Instruction Manual

Radio and General
Range
900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)
Transmit Power
900 MHz: 21 dBm conducted
2.4 GHz: 18 dBm conducted, less than or equal to 20
dBm EIRP
900 MHz Compliance (150 mW Radios)
FCC ID TGUDX80 - This device complies with FCC
Part 15, Subpart C, 15.247
IC: 7044A-DX8009
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with
FCC Part 15, Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Link Timeout
Gateway: Configurable
Node: Defined by Gateway
Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.
Power
Requirements: +10 to 30V dc (Outside the USA: +12 to
24V dc, ±10%). (See UL section below for any applica-
ble UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc
Housing
Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Interface
Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD
Wiring Access
Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector
For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.
Inputs and Outputs
Analog Inputs
Rating: 10V
Impedance: 100 Ohms
Sample Rate: 62.5 milliseconds
Report Rate: 1 second or On Change of State (1%
change in value)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Analog Outputs
Update Rate: 125 milliseconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
To verify the analog input's impedance, use an Ohm meter to
measure the resistance between the analog input terminal (AIx)
and the ground (GND) terminal.
Environmental and Certifications
Ratings
DX80 models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)
DX8x...C (External Wiring Terminal Models)
CSA: Class I, Division 2, Groups A, B, C, D
(Ex/A Ex nA II T4); Certificate: 1921239
LCIE/ATEX: Zone 2 (II 3G / Ex nA IIC); Certifi-
cate: LCIE 10 ATEX 1012 X
SureCross DX80 Node
6 www.bannerengineering.com - tel: 763-544-3164 P/N 136326 Rev. E