Owner's manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 129306 rev. C
SureCross™ DX80K Wireless Configured Kit
Configured input/output mapping
I/O
Point
Terminal Block
Label
DX80 Gateway DX80 Node Terminal Block
Label
I/O
Point
1 DI1 Discrete IN 1 Discrete OUT 1 DO1 9
2 DI2 Discrete IN 2 Discrete OUT 2 DO2 10
3 DI3 Discrete IN 3 Discrete OUT 3 DO3 11
4 DI4 Discrete IN 4 Discrete OUT 4 DO4 12
9 DO1 Discrete OUT 1 Discrete IN 1 DI1 1
10 DO2 Discrete OUT 2 Discrete IN 2 DI2 2
11 DO3 Discrete OUT 3 Discrete IN 3 DI3 3
12 DO4 Discrete OUT 4 Discrete IN 4 DI4 4
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accessories,
please refer to the SureCross™DX80WirelessI/Oproductmanual,Bannerpartnumber132607.
Hookup Diagrams
These are the I/O points as displayed on the device LCD. Any I/O points not shown in the chart are not enabled for this kit.
Sourcing Input Wiring Sourcing Outout Wiring
PWR
GND
DO4
DI4
PWR
GND
DO2
DI2
PWR
GND
DO3
DI3
PWR
GND
DO1
DI1
DIx
PWR
DOx
GND
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/−
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.