Owner's manual
Switches
Device Settings 1 2 3 4 5 6 7 8
Temp °Celsius ON
High resolution (0.1 degree) ** OFF*
Low resolution (1 degree) ON
Platinum, 100 ohm (European, DIN 43760) OFF* OFF* OFF*
Copper, 10 ohm (alpha = 0.00427) OFF ON OFF
* Default configuration
** In high resolution mode, the temperature = (Modbus register value) ÷ 20. In low resolution mode, the temperature is (Modbus register
value) ÷ 2.
Address Mode
The SureCross wireless devices may use one of two types of addressing modes: rotary dial addressing or extended addressing. In
rotary dial address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless network
is restricted to a maximum of 16 devices.
Extended address mode uses a security code to "bind" Nodes to a specific Gateway. Bound Nodes can only send and receive informa-
tion from the Gateway to which they are bound. In extended address mode, wireless networks may contain up to 48 radio devices. For
more information on extended address mode, refer to the SureCross™ Wireless I/O Network product manual.
The device ships in rotary dial address mode by default, with the DIP switch in the OFF position. To use extended address mode, change
the DIP switch to the ON position.
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Temperature Resolution
When set to high resolution, temperature values are stored to the nearest tenth (0.1) of a degree (default position). To measure tempera-
tures above 1600 degrees Fahrenheit or 1600 degrees Celsius, switch the DIP switch to the ON position and use low resolution mode. In
high resolution, the device cannot store values larger than 1600.
Temperature Units
Use the DIP switch to specify if the temperature is stored in degrees Fahrenheit or Celsius. The default position is OFF, setting the
temperature to Fahrenheit. For Celsius measurements, set this switch to the ON position.
RTD Type
Use DIP switches 5, 6, and 7 to select the RTD type. The default position is the OFF position for all switches, setting the RTD to a
Platinum 100 ohm type.
Wiring Your SureCross® Device
Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.
5-pin Euro-Style Wiring (Nodes)
Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.
Wire No. Wire Color 10 to 30V dc Powered Nodes Battery Powered Nodes
1
2
3
4
5
1 Brown 10 to 30V dc
2 White
3 Blue dc common (GND) dc common (GND)
4 Black
5 Gray 3.6 to 5.5V dc
SureCross DX80 FlexPower Node with RTD Inputs
P/N 131597 Rev. I www.bannerengineering.com - tel: 763-544-3164 3