Owner manual

Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
4 P/N 129323 rev. E
SureCross™ DX80K Wireless Configured FlexPower™ Kit
Analog Configuration (Default configuration)
For analog configuration, DIP switch 2 is in the OFF position. Analog configuration has analog IN 1 linked to switch power 1 (SP1) and is
programmable using switches four through eight. Analog input 2 uses the report rate and sample intervals listed in the table below. Discrete
inputs 1 and 2 are also active in this configuration and the input types are defined using switch 3. Two sinking discrete outputs are active for
this configuration.
Analog Configuration, Switch 2 OFF DIP Switches
Descriptions 3 4 5 6 7 8
Discrete Sinking (NPN) OFF*
Discrete Sourcing (PNP) ON
Booster 10V (Analog IN 1) OFF
Booster15V(AnalogIN1) ON*
Warm-up Time 10 milliseconds OFF
Warm-upTime500milliseconds ON*
Sample/Report Rate 1 second OFF OFF OFF
Sample/Report Rate 2 seconds OFF OFF ON
Sample/Report Rate 4 seconds OFF ON OFF
Sample/Report Rate 16 seconds OFF ON ON
Sample/Report Rate 64 seconds ON OFF OFF
Sample/ReportRate5minutes ON OFF ON
Host configured (override switches) ON ON OFF
Sample/ReportRate15minutes ON* ON* ON*
Analog IN 2, Discrete 1, and Discrete 2 are not powered from switched power terminals. In this configuration, SP2 is disabled. If you need SP2, contact the factory.
Discrete Configuration
The discrete configuration matches the switch power outputs (SP1, SP2) with the discrete inputs. The analog inputs are disabled. The discrete
configuration is selected when switch 2 is in the ON position. Two sinking discrete outputs are active for this configuration.
Discrete Configuration, Switch 2 ON DIP Switches
Descriptions 3 4 5 6 7 8
Discrete Sinking (NPN) OFF
Discrete Sourcing (PNP) ON
Booster5V OFF
Booster 10V ON
Warm-up Time 4 milliseconds OFF
Warm-up Time 10 milliseconds ON
Sample/ReportRate62.5milliseconds OFF OFF OFF
Sample/ReportRate125milliseconds OFF OFF ON
Sample/ReportRate250milliseconds OFF ON OFF
Sample/ReportRate500milliseconds OFF ON ON
Sample/Report Rate 1 second ON OFF OFF
Sample/Report Rate 2 seconds ON OFF ON
Host configured (override switches) ON ON OFF
Sample/Report Rate 16 seconds ON ON ON
Notes:DiscreteIN1usesswitchedpower1(SP1).DiscreteIN2usesswitchedpower2(SP2).Analoginputs1and2aredisabled.