Owner's manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 129316 rev. D
SureCross™ DX80K Wireless Configured Kit
Hookup Diagrams
For additional information, including
installation and setup, weatherproofing,
device menu maps, troubleshooting, and
a list of accessories, please refer to the
SureCross™ DX80 Wireless I/O Network
productmanual,Bannerp/n132607.
Sourcing Input Wiring
Sourcing Outout Wiring
Configured input/output mapping
Node 1
Node 2
Gateway as I/O
Repeater
Inputs D1-2, A1-2
Outputs D1-2, A1-2
Inputs D1-2, A1-2
Outputs D1-2, A1-2
An I/O repeater system uses the Gateway to
pass data between Nodes.
Discrete inputs map to discrete outputs and
analog inputs map to analog outputs
I/O
Point
Terminal Block
Label
DX80 Node 1 DX80 Node 2 Terminal Block
Label
I/O
Point
1 DI1 Discrete IN 1 Discrete OUT 1 DO1 9
2 DI2 Discrete IN 2 Discrete OUT 2 DO2 10
5 AI1 Analog IN 1 Analog OUT 1 AO1 13
6 AI2 Analog IN 2 Analog OUT 2 AO2 14
9 DO1 Discrete OUT 1 Discrete IN 1 DI1 1
10 DO2 Discrete OUT 2 Discrete IN 2 DI2 2
13 AO1 Analog OUT 1 Analog IN 1 AI1 5
14 AO2 Analog OUT 2 Analog IN 2 AI2 6
These are the I/O points as displayed on the device LCD. Any I/O points not shown in the chart are not enabled for this kit.
DIx
PWR
PWR
GND
AO2
AI2
PWR
GND
DO2
DI2
PWR
GND
AO1
AI1
PWR
GND
DO1
DI1
DOx
GND
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/−
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.