Owner manual
Modbus/User Configuration Tool (UCT) or DIP Switch Configured
In Modbus/UCT Configured mode, the device parameters are changed using the User Configuration Tool (UCT) or a Modbus command.
All DIP switch positions are ignored. In DIP Switch Configured mode, use the DIP switches to configure the parameters listed in the table.
Wiring Your SureCross® Device
Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.
5-pin Euro-Style Hookup
Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage.
Wire No. Wire Color Description
1
2
3
4
5
1 Brown 10 to 30V dc
2 White RS485 / D1 / B / +
3 Blue dc common (GND)
4 Black RS485 / D0 / A / –
5 Gray Comms Gnd
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.
Terminal Label Gateway, DX85 10 to 30V dc Powered Nodes Battery Powered Nodes
V+ 10 to 30V dc 10 to 30V dc
Tx/+ RS485 / D1 / B / +
V- dc common (GND) dc common (GND) dc common (GND)
Rx/- RS485 / D0 / A / -
B+ 3.6 to 5.5V dc
Terminal Block
When your wireless network does not include a host system, the eight input/four output Gateway must be mapped to the four input/eight
output Node. Connecting dc power to the communication pins will cause permanent damage.
IP67 Housing IP20 Housing
PWR
GND
PWR
GND
DO4
DO3
DO2
DO1
DI8
DI7
DI6
DI5
DI4
DI3
DI2
DI1
DI1
DI2
DI3
DI4
DI5
DI6
V-
V-
V+
V+
DI8
DI7
DO1
DO2
DO3
DO4
Tx/+
Rx/-
DIx. Discrete IN x.
DOx. Discrete OUT x.
RX/-. Serial comms line
TX/+. Serial comms line
SureCross DX80 Gateway
4 www.bannerengineering.com - tel: 763-544-3164 P/N 132157 Rev. H