Instruction Manual

Gateway only systems, the Modbus communication LEDs refer to the communication between the Gateway and its host system (if appli-
cable).
M-GAGE Gateway I/O Mapping
The M-GAGE Gateways are pre-programmed to allow the Gateway's inputs to set the baseline of up to six M-GAGE FlexPower Nodes.
For example, Discrete IN 1 on the Gateway triggers a baseline reading for M-GAGE FlexPower Node 1 (Device ID 1). The Gateway's
inputs 1 through 6 are mapped to Node Device IDs 1 through 6.
The M-GAGE inputs for each FlexPower Node are likewise mapped to the Gateway's discrete outputs by Device ID. M-GAGE Node
Device ID 2 is mapped to the Gateway's Discrete OUT 2. The Gateway's outputs are activated when the M-GAGE sensor is above the
established threshold value.
Use the DX80 User Configuration Tool (UCT) to adjust the M-GAGE sensor parameters.
I/O Terminal Label M-GAGE Gateway M-GAGE Node I/O
1 DI1 Discrete IN 1 to M-GAGE Node 1 Baseline 14
2 DI2 Discrete IN 2 to M-GAGE Node 2 Baseline 14
3 DI3 Discrete IN 3 to M-GAGE Node 3 Baseline 14
4 DI4 Discrete IN 4 to M-GAGE Node 4 Baseline 14
5 DI5 Discrete IN 5 to M-GAGE Node 5 Baseline 14
6 DI5 Discrete IN 6 to M-GAGE Node 6 Baseline 14
9 DO1 Discrete OUT 1 from M-GAGE Node 1 M-GAGE Input 1
10 DO2 Discrete OUT 2 from M-GAGE Node 2 M-GAGE Input 1
11 DO3 Discrete OUT 3 from M-GAGE Node 3 M-GAGE Input 1
12 DO4 Discrete OUT 4 from M-GAGE Node 4 M-GAGE Input 1
13 DO5 Discrete OUT 5 from M-GAGE Node 5 M-GAGE Input 1
14 DO6 Discrete OUT 6 from M-GAGE Node 6 M-GAGE Input 1
Modbus Register Table
I/O
Modbus Holding Register I/O Type I/O Range Holding Register Representa-
tion
Terminal
Block La-
bels
Gateway /
DX85
Any Node Min. Max. Min. (Dec.) Max. (Dec.)
1 1 1 + (Node# × 16) Discrete IN 1 0 1 0 1 DI1
2 2 2 + (Node# × 16) Discrete IN 2 0 1 0 1 DI2
3 3 3 + (Node# × 16) Discrete IN 3 0 1 0 1 DI3
4 4 4 + (Node# × 16) Discrete IN 4 0 1 0 1 DI4
5 5 5 + (Node# × 16) Discrete IN 5 0 1 0 1 DI5
6 6 6 + (Node# × 16) Discrete IN 6 0 1 0 1 DI6
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 0 1 0 1 DO2
11 11 11 + (Node# × 16) Discrete OUT 3 0 1 0 1 DO3
12 12 12 + (Node# × 16) Discrete OUT 4 0 1 0 1 DO4
SureCross DX80 Gateway for M-GAGEs
6 www.bannerengineering.com - tel: 763-544-3164 P/N 134303 Rev. H