User Manual

I/O Modbus Holding Register I/O Type I/O Range Holding Register Representa-
tion
Terminal Block
Labels
Gateway Any Node Min. Max. Min. (Dec.) Max. (Dec.)
11 11 11 + (Node# × 16) Clear Counter 1 0 1 0 1
12 12 12 + (Node# × 16)
13 13 13 + (Node# × 16) Clear Counter 2 0 1 0 1
14 14 14 + (Node# × 16)
15 15 15 + (Node# × 16) Control Message
16 16 16 + (Node# × 16) Reserved
** Two consecutive 16-bit unsigned registers are combined to represent one 32-bit unsigned number for a maximum total count of
4,294,967,295.
High word (I/O 3)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
+
Low word (I/O 4)
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Modbus Register Table (Two Event Counters)
I/O
Modbus Holding Register I/O Type I/O Range Holding Register Representa-
tion
Terminal Block
Labels
Gateway Any Node Min. Max. Min. (Dec.) Max. (Dec.)
1 1 1 + (Node# × 16) Discrete IN 1 0 1 0 1 DI1
2 2 2 + (Node# × 16) Discrete IN 2 0 1 0 1 DI2
3 3 3 + (Node# × 16) Event Count 1 (high)** 0 65535 0 65535
CI1
4 4 4 + (Node# × 16) Event Count 1 (low)** 0 65535 0 65535
5 5 5 + (Node# × 16) Event Count 2 (high)** 0 65535 0 65535
CI2
6 6 6 + (Node# × 16) Event Count 2 (low)** 0 65535 0 65535
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 0 1 0 1 DO2
11 11 11 + (Node# × 16) Clear Counter 1 0 1 0 1
12 12 12 + (Node# × 16)
13 13 13 + (Node# × 16) Clear Counter 2 0 1 0 1
14 14 14 + (Node# × 16)
15 15 15 + (Node# × 16) Control Message
SureCross DX80 FlexPower Counter Node
P/N 136348 Rev. G www.bannerengineering.com - tel: 763-544-3164 7