User Manual

Setting Up Your Wireless Network
To set up and install your wireless network, follow these steps:
1. Configure the DIP switches of all devices.
2. Connect the sensors to the SureCross devices.
3. Apply power to all devices.
4. Form the wireless network by binding the Nodes to the Gateway. If the binding instructions are not included in the datasheet, refer to
the product manual for binding instructions.
5. Observe the LED behavior to verify the devices are communicating with each other.
6. Conduct a site survey between the Gateway and Nodes. If the site survey instructions are not included in this datasheet, refer to the
product manual for detailed site survey instructions.
7. Install your wireless sensor network components. If installation instructions are not included in this datasheet, refer to the product
manual for detailed installation instructions.
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accesso-
ries, refer to one of the following product manuals.
SureCross Quick Start Guide: Banner part number 128185
SureCross Wireless I/O Network Manual: 132607
Web Configurator Manual (used with "Pro" and DX83 models): 134421
Host Configuration Manual 132114
Configuring the DIP Switches
Before making any changes to the DIP switch positions, disconnect the power. DIP switch changes will not be recognized if power isn't
cycled to the device.
For parameters not set via DIP switches, use the User Configuration Tool (UCT) to make configuration changes. For parameters set
using the DIP switches, the DIP switch positions override any changes made using the User Configuration Tool.
DIP Switch Settings
Switches
Device Settings 1 2 5 6 7 8
Rotary switch address mode OFF*
Extended address mode ON
Modbus or UCT configured (overrides switches
3-8)
OFF*
DIP switch configured ON
Discrete IN #1 Sinking (NPN) OFF*
Discrete IN #1 Sourcing (PNP) ON
Discrete IN #2 Sinking (NPN) OFF*
Discrete IN #2 Sourcing (PNP) ON
Counter 2: rate (frequency) counter OFF*
Counter 2: event counter ON
Report Rate 16 seconds OFF*
Report Rate 1 second ON
* Default configuration
SureCross DX80 FlexPower Counter Node
2 www.bannerengineering.com - tel: 763-544-3164 P/N 136348 Rev. G