Owner manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 129312 rev. C
SureCross™ DX80K Wireless Configured Kit
For additional information, including installation and setup, weatherproofing, device menu
maps, troubleshooting, and a list of accessories, please refer to the SureCross™ DX80
WirelessI/ONetworkproductmanual,Bannerpartnumber132607.
I/O
Point
Terminal Block
Label
DX80 Gateway DX80 Node Terminal Block
Label
I/O
Point
1 DI1 Discrete IN 1 Discrete OUT 1 DO1 9
2 DI2 Discrete IN 2 Discrete OUT 2 DO2 10
5 AI1 Analog IN 1 Analog OUT 1 AO1 13
6 AI2 Analog IN 2 Analog OUT 2 AO2 14
9 DO1 Discrete OUT 1 Discrete IN 1 DI1 1
10 DO2 Discrete OUT 2 Discrete IN 2 DI2 2
13 AO1 Analog OUT 1 Analog IN 1 AI1 5
14 AO2 Analog OUT 2 Analog IN 2 AI2 6
Configured input/output mapping
These are the I/O points as displayed on the device LCD. Any I/O points not shown in the chart are not enabled for this kit.
Hookup Diagrams
Sourcing Input Wiring Sourcing Outout Wiring
PWR
AIx
*
* Do not exceed analog input ratings for analog
inputs. Only connect sensor outputs to analog inputs.
AOx
GND
+10 to 30V dc
Analog (Sourcing) Input Wiring
(10 to 30V dc power)
Analog (Sourcing) Output Wiring
PWR
GND
AO2
AI2
PWR
GND
DO2
DI2
PWR
GND
AO1
AI1
PWR
GND
DO1
DI1
DIx
PWR
DOx
GND
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/−
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.