User Manual

Network Connection Errors
Connection errors are internal network related errors and include:
2001 General socket error
2005 Could not reach local DNS to look up remote host
2006 HTTP client aborted a web session
< 200 Unexpected network errors. Contact Banner Engineering if these errors occur.
Error messages that may be returned by the dynamic DNS service(s), noted as last reply, include:
badauth The user name and/or password does not match the host name
nohost The host name specified does not exist
notfqdn The host name is not a fully qualified domain name (not in the form of name.domain.com)
!yours The host name does exist, but not under the user name given
abuse The host name given is blocked for abuse.
Error messages that could be returned by the dynamic DNS service(s) that require the attention of Banner Engineering include:
badsys The sycodestem is not valid
badagent The user agent is not specified or is blocked for non-conformance to specifications
!donator Invalid option specified
numhost Too many or too few hosts found
Error messages indicating a DDNS server error will be either dnserr or 911. In both cases, wait a minimum of 1 hour before restarting the
system, or contact the DDNS service to see when the problem will be resolved.
SureCross Web Configurator
80 www.bannerengineering.com - tel: 763-544-3164 rev. -