Owner manual

I/O Modbus Holding Register I/O Type Units I/O Range Holding Register
Representation
Terminal
Block Labels
Gateway Any Node Min. Max. Min.
(Dec.)
Max.
(Dec.)
1 1 1 + (Node# × 16) Discrete IN 1 - 0 1 0 1 DI1
2 2 2 + (Node# × 16) Discrete IN 2 - 0 1 0 1 DI2
3 3 3 + (Node# × 16) Analog IN 1+ mA / V 0.0 20.0 /
10.0
0 65535 A1+
4 4 4 + (Node# × 16) Analog IN 2+ mA / V 0.0 20.0 /
10.0
0 65535 A2+
5 5 5 + (Node# × 16) Analog IN 3+ mA / V 0.0 20.0 /
10.0
0 65535 A3+
6 6 6 + (Node# × 16) Analog IN 4+ mA / V 0.0 20.0 /
10.0
0 65535 A4+
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 - 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 - 0 1 0 1 DO2
...
15 15 15 + (Node# × 16) Control Message
16 16 16 + (Node# × 16) Reserved
Specifications
Radio and General
Range
900 MHz: Up to 4.8 kilometers (3 miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)
Transmit Power
900 MHz: 21 dBm conducted
2.4 GHz: 18 dBm conducted, less than or equal to 20
dBm EIRP
900 MHz Compliance (150 mW Radios)
FCC ID TGUDX80 - This device complies with FCC
Part 15, Subpart C, 15.247
IC: 7044A-DX8009
2.4 GHz Compliance
FCC ID UE300DX80-2400 - This device complies with
FCC Part 15, Subpart C, 15.247
ETSI/EN: In accordance with EN 300 328: V1.7.1
(2006-05)
IC: 7044A-DX8024
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Link Timeout
Gateway: Configurable
Node: Defined by Gateway
Power
Requirements: +10 to 30V dc or +3.6 to 5.5V dc low
power option (Outside the USA: +12 to 24V dc, ±10%
or +3.6 to 5.5V dc low power option)
Consumption: Less than 1.4 W (60 mA) at 24V dc
Housing
Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Interface
Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD
Wiring Access
Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector
SureCross DX80 FlexPower Node
6 www.bannerengineering.com - tel: 763-544-3164 P/N 131762 Rev. I