Instruction Manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
6 P/N 129322 rev. E
SureCross™ DX80K Wireless Configured FlexPower™ Kit
General
Power*
Gateway and Node:+10to30Vdc(ForEuropeanapplications:+10to24Vdc,±10%)
FlexPower™ Node:+3.6to5.5Vdclowpoweroption
Power Consumption
Less than 1.4 W (60 mA) at 24V dc
Mounting
#10orM5(M5hardwareincluded)
M5FastenersMax.TighteningTorque
0.56N•m(5in•lbf)
Case Material
Polycarbonate
Weight
0.26kg(0.57lb.)
Indicators
Two LED, bi-color
Switches
Two Push Buttons
Display
Six Character LCD
External Cable Glands
FourPG-7type,One1/2-inchNPTtype
Cable Glands Max. Tightening Torque
0.56N•m(5in•lbf)
* ForEuropeanapplications,powertheDX80fromaLimitedPowerSourceasdenedinEN60950-1.
Specifications
Radio
Range*
900 MHz:Upto4.8kilometers(3miles)
2.4 GHz: Up to 3.2 kilometers (2 miles)
Transmit Power
900 MHz: 21 dBm Conducted
2.4 GHz: 18 dBm Conducted, ≤ 20 dBm EIRP
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Antenna Connector
Ext.ReversePolaritySMA,50Ohms
Antenna Max. Tightening Torque
0.45N•m(4in•lbf)
Link Timeout
64 seconds
* With the standard 2 dB antenna. High-gain antennas are available, but the range depends on the environment and line of sight. To determine the range of your wireless
network, perform a Site Survey.
Many parameters are configurable. The values in the tables represent factory defaults unless otherwise noted.
Inputs
Discrete Inputs
Two Sinking
Discrete Input Rating
3 mA max current at 30V dc
Discrete Input 1 Sample Rate
250milliseconds(switchselectable)
Discrete Input 2 Sample Rate
250milliseconds(switchselectable)
Discrete Input 1,2 Report Rates
On Change of State
Discrete Input ON Condition
Lessthan0.7V
Discrete Input OFF Condition
Greater than 2V or Open
Switched Power for Input 1
5V