Instruction Manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
4 P/N 129322 rev. E
SureCross™ DX80K Wireless Configured FlexPower™ Kit
Analog Configuration
For analog configuration, DIP switch 2 is in the OFF position. Analog configuration has analog IN 1 linked to switch power 1 (SP1) and is
programmable using switches four through eight. Analog input 2 uses the report rate and sample intervals listed in the table below. Discrete
inputs 1 and 2 are also active in this configuration and the input types are defined using switch 3. Two sinking discrete outputs are active for
this configuration.
Analog Configuration, Switch 2 OFF DIP Switches
Descriptions 3 4 5 6 7 8
Discrete Sinking (NPN) OFF*
Discrete Sourcing (PNP) ON
Booster 10V (Analog IN 1) OFF*
Booster15V(AnalogIN1) ON
Warm-up Time 10 milliseconds OFF*
Warm-upTime500milliseconds ON
Sample/Report Rate 1 second OFF OFF OFF
Sample/Report Rate 2 seconds OFF OFF ON
Sample/Report Rate 4 seconds OFF ON OFF
Sample/Report Rate 16 seconds OFF ON ON
Sample/Report Rate 64 seconds ON OFF OFF
Sample/ReportRate5minutes ON OFF ON
Host configured (override switches) ON ON OFF
Sample/ReportRate15minutes ON ON ON
Analog IN 2, Discrete 1, and Discrete 2 are not powered from switched power terminals. In this configuration, SP2 is disabled. If you need SP2, contact the factory.
Discrete Configuration (default configuration)
The discrete configuration matches the switch power outputs (SP1, SP2) with the discrete inputs. The analog inputs are disabled. The discrete
configuration is selected when switch 2 is in the ON position. Two sinking discrete outputs are active for this configuration.
Discrete Configuration, Switch 2 ON DIP Switches
Descriptions 3 4 5 6 7 8
Discrete Sinking (NPN) OFF*
Discrete Sourcing (PNP) ON
Booster5V OFF*
Booster 10V ON
Warm-up Time 4 milliseconds OFF*
Warm-up Time 10 milliseconds ON
Sample/ReportRate62.5milliseconds OFF OFF OFF
Sample/ReportRate125milliseconds OFF OFF ON
Sample/ReportRate250milliseconds* OFF* ON* OFF*
Sample/ReportRate500milliseconds OFF ON ON
Sample/Report Rate 1 second ON OFF OFF
Sample/Report Rate 2 seconds ON OFF ON
Host configured (override switches) ON ON OFF
Sample/Report Rate 16 seconds ON ON ON
Notes:DiscreteIN1usesswitchedpower1(SP1).DiscreteIN2usesswitchedpower2(SP2).Analoginputs1and2aredisabled.(DefaultcongurationforthePE1kits)