Owner's manual
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 129307 rev. C
SureCross™ DX80K Wireless Configured Kit
I/O
Point
Terminal Block
Label
DX80 Gateway DX80 Node Terminal Block
Label
I/O
Point
1 DI1 Discrete IN 1 Discrete OUT 1 DO1 9
Node 1
2 DI2 Discrete IN 2 Discrete OUT 2 DO2 10
3 DI3 Discrete IN 3 Discrete OUT 1 DO1 9
Node 2
4 DI4 Discrete IN 4 Discrete OUT 2 DO2 10
9 DO1 Discrete OUT 1 Discrete IN 1 DI1 1
Node 1
10 DO2 Discrete OUT 2 Discrete IN 2 DI2 2
11 DO3 Discrete OUT 3 Discrete IN 1 DI1 1
Node 2
12 DO4 Discrete OUT 4 Discrete IN 2 DI2 2
Configured input/output mapping
These are the I/O points as displayed on the device LCD. Any I/O points not shown in the chart are not enabled for this kit.
Sourcing Input Wiring Sourcing Output Wiring
For additional information, including installation and setup, weatherproofing, device menu maps, troubleshooting, and a list of accessories,
pleaserefertotheSureCross™DX80WirelessI/ONetworkproductmanual,Bannerpartnumber132607.
Hookup Diagrams
DIx
PWR
DOx
GND
PWR
GND
DO4
DI4
PWR
GND
DO2
DI2
PWR
GND
DO3
DI3
PWR
GND
DO1
DI1
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/−
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.