Owner manual

Wiring Your SureCross® Device
Use the following wiring diagrams to first wire the sensors and then apply power to the SureCross devices.
5-pin Euro-Style Wiring (Nodes)
Wiring the 5-pin Euro-style connector depends on the model and power requirements of the device. Connecting dc power to the commu-
nication pins will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.
Wire No. Wire Color 10 to 30V dc Powered Nodes Battery Powered Nodes
1
2
3
4
5
1 Brown 10 to 30V dc
2 White
3 Blue dc common (GND) dc common (GND)
4 Black
5 Gray 3.6 to 5.5V dc
DX80...C Wiring
Wiring power to the DX80...C models varies depending the power requirements of the model. Connecting dc power to the communication
pins (Tx/Rx) will cause permanent damage. For FlexPower devices, do not apply more than 5.5V to the gray wire.
Terminal Label Gateway, DX85 10 to 30V dc Powered Nodes Battery Powered Nodes
V+ 10 to 30V dc 10 to 30V dc
Tx/+ RS485 / D1 / B / +
V- dc common (GND) dc common (GND) dc common (GND)
Rx/- RS485 / D0 / A / -
B+ 3.6 to 5.5V dc
Terminal Blocks (IP67 and IP20 Base)
IP67 Base IP20 Base
DI1
DO1
GND
SP3
GND
A1+
A1
SP1
DI2
DO2
GND
SP4
GND
A2+
A2
SP2
DI1
DI2
SP1
SP2
A1
A2
V+
V
V
DO1
DO2
SP3
SP4
A1+
A2+
TX/+
RX/
B+
Ax+ and Ax-. Analog IN x. Analog inputs for devices requiring
more than one connection, such as thermocouples or RTDs.
When there is no Ax-, use Ax+ as an analog input.
DIx. Discrete IN x.
DOx. Discrete OUT x.
GND. Ground/dc common connection.
B+. 3.6 to 5.5V dc (for battery powered models only).
RX/-. Serial comms line
TX/+. Serial comms line
V+. Power, 10 to 30V dc power connection.
V-. Ground/dc common connection.
SureCross DX80 FlexPower Node
P/N 131296 Rev. L www.bannerengineering.com - tel: 763-544-3164 5