Manual
Inputs and Outputs
Discrete Inputs
Rating: 3 mA max current at 30V dc
Sample Rate: 62.5 milliseconds
Report Rate: On change of state
Discrete Input ON Condition
PNP: Greater than 8V
NPN: Less than 0.7V
Discrete Input OFF Condition
PNP: Less than 5V
NPN: Greater than 2V or open
Analog Inputs
Rating: 24 mA
Impedance: 100 Ohms
Sample Rate: 62.5 milliseconds
Report Rate: 1 second or On Change of State (1%
change in value)
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
Discrete Outputs
Update Rate: 125 milliseconds
ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: OFF
Discrete Output Rating (PNP)
100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA
Analog Outputs
Update Rate: 125 milliseconds
Accuracy: 0.1% of full scale +0.01% per °C
Resolution: 12-bit
To verify the analog input's impedance, use an Ohm meter to
measure the resistance between the analog input terminal (AIx)
and the ground (GND) terminal.
Communication and Environmental
Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k
Data format: 8 data bits, no parity, 1 stop bit
Protocol
Modbus RTU
Refer to the SureCross DX80 Wireless I/O Network Product Man-
ual (p/n 132607) for installation and waterproofing instructions. Op-
erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.
Environmental Rating
DX80 Models:IEC IP67; NEMA 6; (See UL section be-
low for any applicable UL specifications)
DX80...C Models: IEC IP20; NEMA 1 (In a suitable en-
closure: Class I, Division 2, Group A, B, C, D; T4 −40
to 80 °C)
Operating Environment
Temperature: −40 to +85 °C (Electronics); −20 to +80
°C (LCD)
Humidity: 95% max. relative (non-condensing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
Certifications
DX8x...C (External Wiring Terminal Models)
CSA: Class I, Division 2, Groups A, B, C, D
(Ex/A Ex nA II T4); Certificate: 1921239
LCIE/ATEX: Zone 2 (II 3G / Ex nA IIC); Certifi-
cate: LCIE 10 ATEX 1012 X
UL Listing
Maximum ambient temperature: 70 °C
Mounting instructions: See document 132607
Power rating: 10 to 30V dc, UL Class 2
Enclosure environmental rating: UL Type 1
Included with Model
The following items ship with the DX80 radios.
SureCross DX80 Gateway with Discrete and Analog I/O
P/N 131935 Rev. H www.bannerengineering.com - tel: 763-544-3164 7