User Manual

Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
6 P/N 137909 rev. A
SureCross™ DX80K Wireless Configured Kit
It is Banner Engineering’s intent to fully comply with all national and regional regulations regarding radio frequency emissions. Customers who want to re-export this
product to a country other than that to which it was sold must ensure that the device is approved in the destination country. A list of approved countries appears in the
SureCross DX80 Wireless Product Manual, in the Agency Certifications section. Consult with Banner Engineering if the destination country is not on this list.
Certifications, Radio
900 MHz Models
FCCIDTGUDX80:ThisdevicecomplieswithFCCPart15,SubpartC,15.247
IC: 7044A-DX8009
2.4 GHz Models
FCCIDUE300DX80-2400:ThisdevicecomplieswithFCCPart15,SubpartC,15.247
ETSI/EN:InaccordancewithEN300328:V1.7.1(2006-05)
IC: 7044A-DX8024
Environmental
Environmental Rating*
IECIP67;NEMA6
Operating Temperature**
−40to+85°C(Electronics);−20to+80°C(LCD)
Operating Humidity
95%max.relative(non-condensing)
Radiated Immunity
10V/m,80-2700MHz(EN61000-6-2)
Shock and Vibration
IEC68-2-6andIEC68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration:0.5mmp-p,10to60Hz
* PleaserefertotheSureCross™DX80WirelessI/ONetworkproductmanual,Bannerp/n132607,forinstallationandwaterproonginstructions.
** Operating the devices at the maximum operating conditions for extended periods can shorten the life of the device.
Outputs
Discrete Outputs
Gateway: Four Sourcing
Node: Two Sourcing
Discrete Output Rating
100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 µA
Discrete Output ON Condition
Supply minus 2V
Discrete Output OFF Condition
Less than 2V
Discrete Output State Following Timeout
De-energized (OFF)
Analog Outputs
Gateway: Two, 0 to 20 mA
Node: One, 0 to 20 mA
Discrete, Analog Update Rate
62.5milliseconds
Maximum End-to-End Latency*
200 milliseconds
Output State Following Timeout
De-energized (OFF)
* From the sample point and with a good RF signal.