User Manual

Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
2 P/N 137909 rev. A
SureCross™ DX80K Wireless Configured Kit
Hookup Diagrams
Sourcing Input Wiring
Sourcing Output Wiring
I/O
Point
Terminal
Block Label
DX80 Gateway DX80 Node Terminal
Block Label
I/O
Point
1 DI1 Discrete IN 1 Discrete OUT 1 DO1 9
Node 1
2 DI2 Discrete IN 2 Discrete OUT 2 DO2 10
3 DI3 Discrete IN 3 Discrete OUT 1 DO1 9
Node 2
4 DI4 Discrete IN 4 Discrete OUT 2 DO2 10
5 AI1 Analog IN 1 Analog OUT 1 AO1 13 Node 1
6 AI2 Analog IN 2 Analog OUT 2 AO2 14 Node 2
9 DO1 Discrete OUT 1 Discrete IN 1 DI1 1
Node 1
10 DO2 Discrete OUT 2 Discrete IN 2 DI2 2
11 DO3 Discrete OUT 3 Discrete IN 1 DI1 1
Node 2
12 DO4 Discrete OUT 4 Discrete IN 2 DI2 2
13 AO1 Analog OUT 1 Analog IN 1 AI1 5 Node 1
14 AO2 Analog OUT 2 Analog IN 2 AI2 6 Node 2
Configured input/output mapping
Analog Sourcing Input Wiring
Analog Sourcing Output Wiring
PWR
AIx
*
* Do not exceed analog input ratings for analog
inputs. Only connect sensor outputs to analog inputs.
AOx
GND
+10 to 30V dc
PWR
GND
AO2
AO1
DO4
DO3
DO2
DO1
PWR
GND
AI2
AI1
DI4
DI3
DI2
DI1
DIx
PWR
DOx
GND
5-pin Euro-style Hookup (RS-485)
Wire Color Gateway 10–30V dc Node
1 Brown +10 to 30V dc Input +10 to 30V dc Input
2 White RS485/D1/B/+
3 Blue dc common (GND) dc common (GND)
4 Black RS485/D0/A/−
5 Gray Comms grnd
* Connecting dc power to the communication pins will cause permanent damage.