Manual
Discrete Output Wiring (PNP)
DOx
GND
PWR
10-30V dc
Load
dc common
LED Behavior for the Nodes
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. A Node will not sample its
inputs until it is communicating with its Gateway. When testing communication between the Gateway and Node, all radios and antennas
should be at least two meters apart or the communications may fail.
LED 1 LED 2 Node Status
(flashing green)
Radio Link Ok
(flashing red) (flashing red)
Device Error
(flashing red, 1 per 3 sec)
No Radio Link
Modbus Register Table
When your wireless network does not include a host system, the eight input/four output Node must be mapped to the four input/eight
output Gateway.
I/O
Point
Modbus Holding Register I/O Type I/O Range Holding Register Representa-
tion
Terminal
Block Labels
Gateway/
DX85
Any Node Min. Max. Min. (Dec.) Max. (Dec.)
1 1 1 + (Node# × 16) Discrete IN 1–8 0 ** 0 255 DI1
...
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 0 1 0 1 DO2
11 11 11 + (Node# × 16) Discrete OUT 3 0 1 0 1 DO3
12 12 12 + (Node# × 16) Discrete OUT 4 0 1 0 1 DO4
...
15 15 15 + (Node# × 16) Control Message
16 16 16 + (Node# × 16) Reserved
The lower eight bits of the 16-bit unsigned register repre-
sent each of the eight digital inputs. Therefore, if all inputs
are OFF (0) the register contains 0x0000; if all inputs are
ON (1) the register contains 0x00FF (255).
Input 8
Input 2
Input 1
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
SureCross DX80 Node with Discrete I/O
P/N 132160 rev. H www.bannerengineering.com - tel: 763-544-3164 5