Manual
Radio and General
900 MHz Compliance (150 mW Radios)
FCC ID TGUDX80 - This device complies with FCC
Part 15, Subpart C, 15.247
IC: 7044A-DX8009
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Antenna Connection
Ext. Reverse Polarity SMA, 50 Ohms
Max Tightening Torque: 0.45 N·m (4 lbf·in)
Radio range is with the 2 dB antenna that ships with the product.
High-gain antennas are available, but the range depends on the
environment and line of sight. To determine the range of your wire-
less network, perform a Site Survey.
Housing
Polycarbonate housing and rotary dial cover; polyester
labels; EDPM rubber cover gasket; nitrile rubber, non-
sulphur cured button covers
Weight: 0.26 kg (0.57 lbs)
Mounting: #10 or M5 (SS M5 hardware included)
Max. Tightening Torque: 0.56 N·m (5 lbf·in)
Link Timeout
Gateway: Configurable
Node: Defined by Gateway
Interface
Indicators: Two bi-color LEDs
Buttons: Two
Display: Six character LCD
Wiring Access
Four PG-7, One 1/2-inch NPT, One 5-pin Euro-style
male connector
For European applications, power the DX80 from a Limited Power
Source as defined in EN 60950-1.
Inputs and Outputs
Discrete Inputs
Rating: 3 mA max current at 30V dc
Sample Rate: 62.5 milliseconds
Report Rate: On change of state
Discrete Input ON Condition
PNP: Greater than 8V
NPN: Less than 0.7V
Discrete Input OFF Condition
PNP: Less than 5V
NPN: Greater than 2V or open
Discrete Outputs
Update Rate: 125 milliseconds
ON Condition: Supply minus 2V
OFF Condition: Less than 2V
Output State Following Timeout: De-energized (OFF)
Discrete Output Rating (PNP)
100 mA max current at 30V dc
ON-State Saturation: Less than 3V at 100 mA
OFF-state Leakage: Less than 10 μA
Communication and Environmental
Hardware (RS-485)
Interface: 2-wire half-duplex RS-485
Baud rates: 9.6k, 19.2k (default), or 38.4k
Data format: 8 data bits, no parity, 1 stop bit
Protocol
Modbus RTU
Refer to the SureCross DX80 Wireless I/O Network Product Man-
ual (p/n 132607) for installation and waterproofing instructions. Op-
erating the devices at the maximum operating conditions for exten-
ded periods can shorten the life of the device.
Environmental
Rating: IEC IP67; NEMA 6; (See UL section below for
any applicable UL specifications)
Operating Temperature: −40 to +85 °C (Electronics);
−20 to +80 °C (LCD)
Operating Humidity: 95% max. relative (non-condens-
ing)
Radiated Immunity: 10 V/m, 80-2700 MHz
(EN61000-6-2)
Shock and Vibration
IEC 68-2-6 and IEC 68-2-7
Shock: 30g, 11 millisecond half sine wave, 18 shocks
Vibration: 0.5 mm p-p, 10 to 60 Hz
SureCross DX80 Gateway