Manual
LED Behavior for the Gateways
After powering up and binding the Gateway and its Nodes, verify all devices are communicating properly. When testing communication
between the Gateway and Node, all radios and antennas should be at least two meters apart or the communications may fail.
LED 1 LED 2 Gateway Status
(solid green)
Power ON
(flashing red) (flashing red)
Device Error
(flashing yellow)
Modbus Communication Active
(flashing red)
Modbus Communication Error
For Gateway and Ethernet Bridge systems, active Modbus communication refers to the communication between the Gateway and the
Ethernet Bridge. For GatewayPro systems, the Modbus communication LEDs refer to the communication internal to the GatewayPro. For
Gateway only systems, the Modbus communication LEDs refer to the communication between the Gateway and its host system (if appli-
cable).
Modbus Register Table
I/O #
Modbus Holding Register I/O Type I/O Range Holding Register Rep-
resentation
Terminal
Block Labels
Gateway Any Node Min. Value Max. Val-
ue
Min.
(Dec.)
Max. (Dec.)
1 1 1 + (Node# × 16) Discrete IN 1 0 1 0 1 DI1
2 2 2 + (Node# × 16) Discrete IN 2 0 1 0 1 DI2
3 3 3 + (Node# × 16) Discrete IN 3 0 1 0 1 DI3
4 4 4 + (Node# × 16) Discrete IN 4 0 1 0 1 DI4
...
7 7 7 + (Node# × 16) Reserved
8 8 8 + (Node# × 16) Device Message
9 9 9 + (Node# × 16) Discrete OUT 1 0 1 0 1 DO1
10 10 10 + (Node# × 16) Discrete OUT 2 0 1 0 1 DO2
11 11 11 + (Node# × 16) Discrete OUT 3 0 1 0 1 DO3
12 12 12 + (Node# × 16) Discrete OUT 4 0 1 0 1 DO4
...
15 15 15 + (Node# × 16) Control Message
16 16 16 + (Node# × 16) Reserved
Specifications
Radio and General
Range
900 MHz: Up to 4.8 kilometers (3 miles)
Transmit Power
900 MHz: 21 dBm (150 mW) conducted
Power
Requirements: +10 to 30V dc (Outside the USA: +12 to
24V dc, ±10%). (See UL section below for any applica-
ble UL specifications)
Consumption: Less than 1.4 W (60 mA) at 24V dc
SureCross DX80 Gateway
P/N 131291 Rev. F www.bannerengineering.com - tel: 763-544-3164 5