Specifications
Many of the DX80 parameters are configurable. The values in the tables represent factory defaults unless otherwise noted.
General
Power
3.6V dc from an internal battery*
Mounting
#10 or M5 (M5 hardware included)
M5 Fasteners Max. Tightening Torque
0.56N•m(5in•lbf)
Case Material
Polycarbonate
Weight
Indicators
Two LED, bi-color
Switches
Two Push Buttons
Display
Six Character LCD
Inputs
Discrete Inputs
One (Sinking, Sourcing), DIP Switch Selectable
Discrete Input Rating
3 mA max current at 30V dc
Discrete Input Sample Rate
62.5 milliseconds
Discrete Input Report Rate
On Change of State
Discrete Input ON Condition
Sourcing: Greater than 8V
Sinking: Less than 0.7V
Discrete Input OFF Condition
Sourcing: Less than 5V
Sinking: Greater than 2V or Open
Outputs
Discrete Outputs
Three NMOS Sinking
Discrete Output Rating
Less than 10 mA max current at 30V
ON-State Saturation: Less than 0.7V at 20 mA
Discrete Output Update Rate
Up to 1 per second
Discrete Output ON Condition
Less than 0.7V
Discrete Output OFF Condition
Open
Discrete Output State Following Timeout
De-energized (OFF)
Radio
Range, with standard 2 dB antenna*
900 MHz: 300 meters (1000 ft)
2.4 GHz: 300 meters (1000 ft)
Frequency
900 MHz: 902 to 928 MHz ISM band
2.4 GHz: 2.4 to 2.4835 GHz ISM Band
Transmit Power
900 MHz: 21 dBm Conducted
2.4 GHz: 18 dBm Conducted, ≤ 20 dBm EIRP
Spread Spectrum Technology
FHSS (Frequency Hopping Spread Spectrum)
Link Timeout
Defined by Gateway
* The range depends on the environment and line of sight.