User guide
Banner Engineering Corp.•Minneapolis,MNU.S.A
www.bannerengineering.com•Tel:763.544.3164
6 P/N 131598 rev. F
SureCross™ DX80 M-GAGE™ Node with Integrated Battery
M-GAGE Gateway DIP Switches
The special M-GAGE Gateway, models DX80G*M6*6P6ZP, can configure up to two M-GAGE Nodes. To use the special M-GAGE Gateway’s
DIPswitchestoconguretheM-GAGENode,refertotheM-GAGEGatewaydatasheet,Bannerp/n139075.
Configuration Using Register 13
A host system can configure the M-GAGE Node by setting I/O 13 on the M-GAGE Node. Writing a defined value to the Modbus register sets
the M-GAGE operation immediately. The following parameters can be configured by writing to the M-GAGE Node Modbus register 13. The host
system must resend the configuration settings if power is cycled to the wireless system.
Modbus Register 13
Low Pass Filter Sample High
Counter
Report
Rate
Sample Rate Baseline
Filter
Threshold and
Hysteresis
Device Settings 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
No Change
0 0 0
No Low Pass Filter
0 0 1
Low Pass Filter T0
0 1 0
Low Pass Filter T1
0 1 1
Low Pass Filter T2
1 0 0
Low Pass Filter T3
1 0 1
Low Pass Filter T4
1 1 0
Low Pass Filter T6
1 1 1
No Change
0 0 0
1
0 0 1
2
0 1 0
3
0 1 1
4
1 0 0
8
1 0 1
16
1 1 0
32
1 1 1
No Change
0 0
Change of State
0 1
16 sec
1 0
Sample Rate
1 1
No Change
0 0 0
62.5 ms
0 0 1
125 ms
0 1 0
250 ms
0 1 1
500 ms
1 0 0
1 sec
1 0 1
31 ms
1 1 0
20 ms
1 1 1
No Change
0 0