SureCross™ DX80 M-GAGE™ Node with Integrated Battery
Configuration
There are four ways to configure an M-GAGE™Node:
M-GAGE Node DIP switches1.
M-GAGEGatewayDIPswitches(seeBannerdocumentp/n139075formoreinformation)2.
M-GAGE configuration using the M-GAGE Node register 13 3.
Modbusregisters7,15,and16tosendModbuscongurationcommands(seeBannerdocumentp/n132114formoreinformation)4.
M-GAGE Node DIP Switches
The DIP switches on the M-GAGE board change the configuration of the device. After making any changes to the DIP switches, cycle power to
the device to activate the changes.
In Rotary Switch address mode, the left rotary dial establishes the network ID and the right rotary dial sets the device ID. The wireless
network is restricted to a maximum of 16 devices. Extended addressing mode allows for specific Node to Gateway binding and allows network
expansion for more than 16 devices in a wireless network. For most users, this switch is OFF. For more information on extended address
mode,refertotheSureCross™WirelessI/ONetworkproductmanual,p/n132607.BecausetheM-GAGEhasnoLCD,triple-clickbutton2to
activatebindingmodeinsteadofusingthemenustructurelistedindocument132607.
Setting the Node’s Use Switch Settings DIP switch (DIP switch 2) to the ON position allows the Node DIP switches 3 through 8 to be used for
configuration. Configuration settings from the M-GAGE Gateway’s DIP switches are active regardless of the Node’s Use Switch Settings DIP
switch position.
Set the Node’s Use Switch Settings DIP switch to the OFF position to use either the Web Configuration tool to set the parameters or to send
commands to I/O 13 directly from the host system.
Switches
Device Settings 1 2 3 4 5 6 7 8
Rotary Switch Address Mode OFF*
Extended Address Mode ON
Use Configuration OFF*
Use Switch Settings ON
Low Pass Filter T2 OFF* OFF*
Low Pass Filter T3 OFF ON
Low Pass Filter T0 ON OFF
Low Pass Filter T1 ON ON
Sample High Count 4 OFF* OFF*
Sample High Count 8 OFF ON
Sample High Count 1 ON OFF
Sample High Count 2 ON ON
Sample 250 milliseconds OFF* OFF*
Sample 500 milliseconds OFF ON
Sample 1 second ON OFF
Sample 125 milliseconds ON ON
* Default configuration