Owner's manual

Rope Pull Emergency Stop Switches RP-LS42F-75L.. Series
P/N 67709 rev. A 7
Banner Engineering Corp. • Minneapolis,MN U.S.A.
www.bannerengineering.com  •  Tel: 763.544.3164
E-Stop Reset
E-Stop and Latch Reset
Following the pulling of the rope or the pressing of the E-stop button (model RP-LS42F-
75LE), the latch must be reset. The procedure differs slightly between the two models. 
See Figure 6.
Models RP-LS42F-75L and RP-LS42F-75LF:Pull the blue reset button; the arrows 
should then be centered in the tensioning indicator window. 
Model RP-LS42F-75LE:The E-stop can be reset only when proper tension is indicated. 
Turn the yellow knob clockwise until the blue arrow is in the “I” position (indicating that 
the latch has been reset). The latch should make an audible click when reset.
Maintenance
Each rope pull emergency stop installation should be tested for proper machine 
shutdown response at each shift change or machine setup by a Designated Person*.
In addition, a Qualified Person*should check for proper rope tension, and adjust as 
needed, on a periodic schedule determined by the user, based upon severity of the 
operating environment and the frequency of switch actuations.
The pulleys and other moving parts associated with the rope should be periodically 
lubricated. If inspection reveals dirt on the rope pull switch or rope assembly, the dirt 
must be cleaned off and its cause must be eliminated. Replace the rope pull switch 
and/or rope assembly when any parts (including contacts) or assemblies are found to be 
damaged, broken, deformed, or badly worn.
The rope pull switch and rope assembly should be replaced at specified intervals based 
upon the environment and operating conditions. Replacement of the rope pull switch and 
rope assembly should be considered after no more than 500,000 operations. Always 
test the control system for proper functioning under machine control conditions after 
maintenance or replacement of the rope pull switch.
* A Designated Personis identified in writing by the employer as being appropriately trained to perform 
a specified checkout procedure. AQualified Person possesses a recognized degree or certificate 
or has extensive knowledge, training, and experience to be able to solve problems relating to the 
emergency stop rope pull switch installation.
Repairs
Banner rope pull emergency stop switches have no field-replaceable components.  
Contact the Banner Factory Application Engineering Group at the address or the 
numbers listed at the bottom of the back page. They will issue an RMA (Return 
Merchandise Authorization) number for your paperwork, and give you the proper shipping 
address.
Figure 7. Resetting the latch
Model RP-LS42F-75L
and RP-LS42F-75LF
Model RP-LS42F-75LE
Pull
Turn clockwise
to reset
NOTE: Proper rope tension must
be displayed before latch
can be reset