Owner's manual

Rope Pull Emergency Stop Switches RP-LS42F-75L.. Series
6 P/N 67709 rev. A
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com  •  Tel: 763.544.3164
Electrical Installation
Access to Wiring Chamber
The wiring chamber is accessed via the hinged door. Simply insert a flat-blade 
screwdriver, as shown in Figure 5, and pry gently down to open. Select the best wiring
entrance and thread in the ½" x 14 NPSM conduit adapter (supplied), or the optional
M20 x 1.5 cable gland (page 11). The switch knockout will break loose with the final turn 
of the conduit adapter or cable gland.
Figure 5. Access to wiring chamber – use a small flat-blade screwdriver
To connect wires to terminals:
1.  Insert the screwdriver blade into the slot below the 
desired wiring terminal.
2.  Twist the screwdriver blade in the slot to open the 
terminal jaws; insert wire.
3. Hold wire in place and remove screwdriver.
Wiring
These switch models have redundant pairs of safety contacts, so they may be wired for
either single-channel or dual-channel output to a safety module or E-stop circuit. Monitor 
contacts, in either case, may be wired as desired to an external alarm device.
Single-Channel Output: Wire contacts 21/22 or 41/42 together to the input of a safety 
module or E-stop circuit.
Dual-Channel Output: Wire contacts 21/22 and 41/42  independently to the two safety 
module inputs (see Figure 6).
Figure 6. Wire the two switch contacts in
series
41 42 33 34
13 14 21 22
Dual-Channel Safety Device
CH 1CH 2
To open wiring chamber:
1.  Insert the screwdriver blade 
into slot in cover to pry cover 
open.