Manual
1) Avoid running remote sensor cables in wireways together with
power-carrying conductors.
Wiring rules:
2) Avoid running remote sensor cables through areas of known ex-
treme electrical interference (electrical "noise").
3) Always use shielded cables and only connect the shield ("drain")
wire at the amplier.
4) When splicing, never combine emitter and receiver wires into a
common cable. (The result will be electrical "crosstalk" within the
cable, which causes a "lock-on" condition of the amplier.)
Miniature Diffuse Mode
Remote Sensor
The SP320D is a rugged, encapsulated, infrared diffuse mode sensor in a miniature plastic package designed to t into very tight loca-
tions. Its performance characteristics are identical to the larger SP300D. It mounts using two #4 (3mm) screws, and is ideal for nearly
any presence sensing application where small size, high performance, and economy are important.
SP320D sensors have hermetically sealed lenses to eliminate internal condensation, and are supplied with 6 feet of extremely exible,
low-prole cable. Units may be washed down without damage.
This sensor is designed for use with Banner MICRO-AMP
®
system MA3-4 and MA3-4P modulated ampliers, MAXI-AMP™ system
CM Series modulated ampliers, and MB Series ampliers.
SP320D
Specications, SP320D
RANGE: up to 12 inches (30cm)
RESPONSE SPEED: a function of the amplier (see below)
OPERATING TEMPERATURE: -40 to +80° C (-40 to +176° F)
EMITTER CHARACTERISTICS: infrared LED, 880nm
CONSTRUCTION: totally encapsulated, hermetically sealed
lenses. Black Valox
®
housing; NEMA 1, 3, 4, 12, and 13.
CABLE: sensors are supplied with 6' of low-prole PVC-covered
4- conductor cable. 30' cables are available by special order.
OPERATING TEMPERATURE RANGE: 0 to +50°C (+32 to +122° F).
Hookup to MB Series Ampliers
Banner remote sensors will connect to any MB Series amplier. The
model MRB chassis (shown) has octal sockets for the amplier and a
BR-2 relay (supplied) and provides power for the sensors and amplier.
Up to four sensors may be connected to one amplier for light-oper-
ated OR or dark operated AND operation. In multiple-sensor hookups,
receivers are wired in parallel and emitters are connected in series (see
example for CM Series modules, next page).
Several MB Series ampliers are available. Each provides a different
output logic function. Refer to the Banner catalog for more informa-
tion.
Chassis models with additional octal sockets are also available. Other
types of output devices, including solid state relays, may be ordered
(see Banner catalog).
P/N 03471C4A
Printed in USA
EXCESS GAIN
BEAM PATTERN
Specications, MB Series Ampliers
POWER SUPPLY REQUIREMENT: 12-18V dc at less than 100mA,
exclusive of load.
MAXIMUM SENSOR LEAD LENGTH: 100 ft. (30 m) maximum;
use separate shielded cables for emitter and receiver.
RESPONSE SPEED: 1 millisecond ON and OFF.
OUTPUT CONFIGURATION: open collector NPN transistor; maximum
on-state current 250mA, maximum off-state leakage current 100 micro-
amps.