Owner manual

3. Check the receiving device setup.
Check the IP address. The device IP subnet must match the sensor IP subnet.
Check the Port number: 20000 - 20009 (not 2000).
Check all rewall and anti-virus software to verify that it is not blocking the sensor's Ethernet socket.
8.6 Troubleshooting Serial Connections
1. Verify the hardware.
Check for breaks in the serial cable.
Use a straight serial cable from the sensor to the PC.
2. Verify that the Communication tool is congured correctly.
Verify that the desired result data has been checked.
3. Check the receiving device setup.
Check the receiving device setup.
Check that the COM port properties on teh receiving device matches the System parameters in the sensor (baud
rate, data bits, parity, stop bits, and ow control).
8.7 Remote Command Channel Configuration
This section describes the commands that are supported to communicate with a Vision sensor. All commands are
case-insensitive
8.7.1 Remote Command Set
All RCC commands are case-insensitive. Valid characters for commands are 7-bit ASCII alphabetic or numeric
characters (A-Z, a-z, 0-9), dash (-) and underscore (_).
All commands have the following structure:
ACTiON OBJECT_IDENTIFIER QUALIFIER(S)
ACTION is an operation the user intends to perform on the OBJECT_IDENTIFIER. There are three possible actions
available:
GET used to retrieve information associated with the named object. This information can be a Boolean value, and
unsigned or signed number, a string or, for complex objects like the Communications tool, a eld-delimited record
that includes other data types.
SET used to assign a value to a named object.
EXEC used to execute a pre-dened functional object or activity in the sensor. Activities may take object identiers
as parameter qualiers.
The table below identies objects that are supported in the current RCC release, their identiers, and the corresponding
actions that they will support. Items highlighted in bold are command keywords. Flag objects are appended with the
FLG sufx, status objects are appended with the STS sufx, and counters are appended with the CNT sufx.
CommentsOptional
Qualiers
Required
Qualiers
Support ActionsObject or
Activity
Identier
System Object,
Component, or
Activity
If no qualiers are
specied, a 30
Timeout (msec)
or
NoneEXECTRIGGERTrigger
second timeout is
used.NOWAIT