Instruction Manual

Output Configuration
the contacts, do not exceed the following max. values
at any time:
Min. voltage: 1V ac/dc
Max. voltage: 60V
Min. current: 5 mA ac/dc
Max. current: 300 mA
Min. power: 5 mW (5 mVA)
Max. power: 7 W (7 VA)
High Current Rating
If higher loads must be switched through one or more
of the contacts, the minimum and maximum values of
the contact(s) changes to:
Min. voltage: 15V ac/dc
Max. voltage: 250V ac / 24V dc, 6A resistive
Min. current: 30 mA ac/dc
Min. power: 0.45 W (0.45 VA)
Max. power: 150 W (1,500 VA)
IEC 60947-5-1: AC-15: 230V ac, 3A: DC-13: 24V dc,
4A
Note: Transient suppression is recommended when switching in-
ductive loads. Install suppressors across load. Never install sup-
pressors across output contacts (see Warning).
Environmental Certifications
Operating Conditions
Temperature: 0° to +50°C (+32° to 122°F)
Max. Relative Humidity: 90% @ 50°C (non-condens-
ing)
Design Standards: EN 60204-1, IEC 61810-1, EN 60255-1, EN
50205
Dimensions for IM-T-9A and IM-T-11A
118.0 mm
(4.65")
84.0 mm
(3.31")
22.5 mm
(0.89")
Machine
Safety
IM-T -9A
13
S1 S2 Y1
23 33
K1
K2
Y2
Ch.1
Ch.2
Y3 S3 S4
Y4 14 24 34
Figure 9. Interface module dimensions
IM-T-9A and IM-T-11A Interface Modules
10 www.bannerengineering.com - tel: 763-544-3164 P/N 062822 Rev. D