Safety Light Curtain Systems Owner's manual

P/N 68413 rev. A 51
Banner Engineering Corp. Minneapolis, U.S.A.
www.bannerengineering.com Tel: 763.544.3164
EZ-SCREEN Point
Instruction Manual
Periodic Checkout Procedures
13.  Remove electrical power to the EZ-SCREEN System. All
OSSD outputs should immediately turn OFF, and should 
not be capable of turning ON until power is re-applied and, 
if in Latch Output mode, a manual reset is performed (Trip 
Output mode requires no manual reset). 
14.  Test the machine stopping response time, using an 
instrument designed for that purpose, to verify that it 
is the same or less than the overall system response 
time specified by the machine manufacturer. (Banner’s
Applications Engineering Department can recommend a 
suitable instrument.)
Do not continue operation until the entire checkout
procedure is complete and all problems are corrected.
WARNING . . .
Do Not Use Machine
Until System Is Working Properly
If all of these checks cannot be verified, do not
attempt to use the EZ-SCREEN System/guarded machine until
the defect or problem has been corrected (see Section 5).  
Attempts to use the guarded machine under such conditions
could result in serious bodily injury or death.
WARNING . . .
Before Applying
Power to the Machine
Verify that the guarded area is clear of personnel
and unwanted materials (such as tools) before applying power
to the guarded machine.
Failure to do so could result in serious bodily injury or death.
6.4 Daily Checkout
Perform this checkout procedure at every shift change,
power-up and machine set-up change. During continuous
machine run periods, this checkout must be performed
at intervals not to exceed 24 hours. ADesignated Person 
or Qualified Person (as defined in the Safety Glossary) must 
perform the procedure; checkout results should be recorded 
and kept on or near the guarded machine, per OSHA
1910.217(e)(1).
1. Verify that access to the guarded area is not possible from
any area not protected by the EZ-SCREEN System. Hard 
guarding, or supplemental presence-sensing devices must 
be installed, wherever needed, to prevent any person from 
reaching around the light grid or entering into the hazard
area. Verify that all supplemental guarding devices and hard 
guarding are in place and operating properly.
2. Verify that the minimum separation distance from the closest
danger point of the guarded machine to the beam is not less
than the separation distance calculated in Section 3.3.1 and
recorded here: ____________.
3.  Verify that it is not possible for a person to stand within the 
guarded area, undetected by the EZ-SCREEN System or 
by other supplemental guarding (as described in ANSI/RIA
R15.06, or other appropriate standards).
4.  Verify that the Reset switch is mounted outside the guarded 
area, out of reach of anyone inside the guarded area, and 
that the key or other means of preventing inadvertent use is 
in place.
5.  Test the effectiveness of the EZ-SCREEN System with 
power ON, using the trip test (Section 6.2).
6.  Initiate machine motion of the guarded machine and, while it 
is moving, use the supplied test piece to block the beam. Do 
not attempt to insert the test piece into the dangerous parts
of the machine. Upon blocking the beam, the dangerous 
parts of the machine should come to a stop with no apparent 
delay. Upon removal of the test piece from the beam, verify 
that the machine does not automatically restart, and 
that the initiation devices must be engaged to restart the 
machine.
7.  With the guarded machine at rest, block the beam and verify 
that it is not possible for the guarded machine to be put into
motion while the test piece is blocking the beam.
8.  Check carefully for external signs of damage or changes to 
the EZ-SCREEN System, the guarded machine, and their 
electrical wiring. Any damage or changes found should be 
immediately reported to management.