Safety Light Curtain Systems Owner's manual

42 P/N 68413 rev. A
Banner Engineering Corp. Minneapolis, U.S.A.
www.bannerengineering.com Tel: 763.544.3164
EZ-SCREEN Point
Instruction Manual
Troubleshooting and Maintenance
Evaluate status indicators per Section 4.3.
5.1 Troubleshooting Lockout Conditions
Alockout condition causes all of the EZ-SCREEN OSSD 
outputs to turn or remain OFF, sending a “stop” signal to the 
guarded machine. Each sensor provides diagnostic error codes 
to assist in the identification of the cause(s) of Lockouts (see 
Figure 5-1). 
The System provides easy methods for determining operating 
problems. A Lockout condition is indicated by the following:
Emitter
Status indicator  Flashing red
Diagnostic display  Error code
Receiver
Reset indicator  OFF
Status indicator  Flashing red
Beam Status indicator  OFF
Diagnostic display  Error code
Recovery Procedures
To recover from a Lockout condition, all errors must be 
corrected and sensor resets must be performed as shown 
below. 
NOTE:  An emitter reset is only required if the emitter is in a 
Lockout condition.
Receiver Reset
Close the receiver Reset switch for 1/4 to 2 seconds and then 
open the switch (per Section 4.2) or power the sensor down, 
wait a second or two, then power it up. 
NOTE:  If the power down/up method is used and the system 
is set for Latch mode, a manual reset, as described in 
Section 4.4, is required to resume full operation.
Emitter Reset
Power the sensor down, wait a second or two, and then power 
it up.