Safety Light Curtain Systems Owner's manual

P/N 68413 rev. A 41
Banner Engineering Corp. Minneapolis, U.S.A.
www.bannerengineering.com Tel: 763.544.3164
EZ-SCREEN Point
Instruction Manual
Operating Instructions
Latch Output Configuration: If the beam becomes blocked
while the System is running with Latch Output mode selected, 
the receiver outputs turn OFF within 24 ms. If the beam then 
becomes clear, the receiver Beam Status indicator will be Green 
and the Reset indicator will single-flash, indicating the System 
is waiting for a manual latch reset. In Latch Output mode, the 
outputs come back ON only when the beam is clear and after a
manual reset. The System will wait for a manual reset; when a 
valid reset signal is received and the beam remains clear, the 
receiver outputs turn ON. To perform a manual reset, close the 
Reset switch for 1/4 to 2 seconds, then open the switch. (For 
switch model MGA-KS0-1, described in Section 2, turn the key 
1/4 turn clockwise, hold for 1/4 to 2 seconds, then turn the key 
counterclockwise to its original position.) 
Internal Faults (Lockouts): If either sensor detects a critical
fault, scanning ceases, the receiver outputs turn OFF and 
diagnostic information is displayed through the sensor’s front
window. See Section 5 for resolution of error/fault conditions. 
4.5 Periodic Checkout Requirements
To ensure continued reliable operation, the System should be 
checked out periodically.
At every shift change, power-up and machine setup change, 
the Daily checkout should be performed; this checkout may be 
performed by a Designated or Qualified Person (see Section 6.4 
for the procedure). 
Semi-annually, the system and its interface to the guarded 
machine should be thoroughly checked out; this checkout must 
be performed by a Qualified Person (see Section 6.5). Acopy of 
these test results should be posted on or near the machine.
Whenever changes are made to the System (either a new 
configuration of the EZ-SCREEN System or changes to the 
machine), the Commissioning Checkout should be performed 
(see Section 6.3).
4.4 Normal Operation
System Power-Up
The System will power up in one of two ways, depending on 
the Trip/Latch output configuration. If the System is set for Trip
output, it will power up and reset automatically; if the System is 
set for Latch output, it will require a manual reset procedure after 
power-up and sensor alignment.
Trip Output Mode Power-Up: When power is applied, each 
sensor will conduct self-tests to detect critical internal faults, 
determine configuration settings, and prepare the System for 
operation. (If either sensor detects a critical fault, scanning 
ceases, the receiver outputs remain OFF and diagnostic 
information is displayed through the sensor’s front window.) 
If no faults are detected, the System will automatically enter 
Alignment mode, with the receiver looking for an optical sync 
pattern from the emitter. If the receiver is aligned and receiving 
the proper sync pattern, it enters Run mode. No manual reset 
operation is required.
Latch Output Mode Power-Up: When power is applied, each 
sensor will conduct self-tests to detect critical internal faults, 
determine configuration settings, and prepare the System for 
operation. (If either sensor detects a critical fault, scanning 
ceases, the receiver outputs remain OFF and diagnostic 
information is displayed through the sensor’s front window.) 
If no faults are detected, the System will automatically enter 
Alignment mode, with the receiver looking for an optical sync 
pattern from the emitter. If the receiver is aligned and receiving 
the proper sync pattern, it begins scanning to determine the 
blocked or clear status of the beam. When the beam is aligned, 
the Yellow Reset indicator will double-flash to indicate the 
System is waiting for a manual reset. After a valid manual reset, 
the System enters Run mode.
During RUN Mode
Trip Output Configuration: If the beam becomes blocked
while the System is running with Trip output mode selected, the 
receiver outputs turn OFF within 24 ms (the maximum System 
response time). If the beam then becomes clear, the receiver 
outputs come back ON. No resets of any kind are needed. All
required machine control resets are provided by the machine 
control circuit.