Safety Light Curtain Systems Owner's manual

20 P/N 68413 rev. A
Banner Engineering Corp. Minneapolis, U.S.A.
www.bannerengineering.com Tel: 763.544.3164
EZ-SCREEN Point
Instruction Manual
System Installation
Supplemental safeguarding is used to make the hazard point
accessible only through the light grid, per ANSI/RIAR15.06. This 
means that mechanical barriers (such as screens or bars) or 
supplemental safeguarding must be installed, wherever needed, 
to prevent any person from entering into or remaining in the 
hazard area undetected. The use of mechanical barriers for this
purpose is called hard guarding (see the Warning at left and
Figure 3-7).
There must be no gaps between the hard guarding and the 
edges of the light grid (that is, the EZ-SCREEN emitter or 
receiver). Also, OSHAspecifies a relationship between the 
distance of the hard guard barrier from the point of operation
and the maximum allowable size of openings in that barrier 
(see OSHA 1910.217, Table O-10). Openings in the hard guard 
material must meet OSHA or other applicable criteria.
Figure 3-7 shows an example of supplemental safeguarding 
inside a robotic work cell. The EZ-SCREEN (emitter and 
receiver) in conjunction with the hard guarding (i.e. the wall 
and the fencing) is the primary safeguarding. Supplemental 
safeguarding (such as a horizontal mounted safety light screen
as an area guard) is required in areas that can not be viewed 
from the EZ-SCREEN Reset switch (i.e. behind the robot and 
the conveyor). Additional supplemental safeguarding may be 
required by the requirements of relevant standards, such as 
preventing clearance or trapping hazards as described by ANSI/
RIA R15.06 (e.g. the safety mat as an area guard between the 
robot, the turntable, and the conveyor).
Figure 3-7. Supplemental safeguarding
WARNING . . .
The Machine Hazard
Must Be Accessible Only Through the
Light Beam(s)
Mechanical barriers (“hard guarding”) or supplemental
safeguarding, as described by the ANSI B11 series of safety
requirements or other appropriate standards, must be installed
wherever needed to prevent any person from:
•  Reaching around, under, or over the light grid and accessing
the hazard, and
•  Entering or remaining anywhere within the guarded area 
without being detected and a stop command being issued to
the guarded machine (see ANSI/RIAR15.06). 
ACCESS-GUARD
Area Guarding
Hard
Guarding
Hard
Guarding
Hard Guarding
Hazard
Area
Guarding
EZ-SCREEN
Reset Switch