User's Manual

SureCross™ DX80 Quick Start Guide
P/N 128185 Rev B 15
Banner Engineering Corp. • Minneapolis, MN U.S.A.
www.bannerengineering.com Tel: 763.544.3164
Setting up the Network and Device IDs, powering up the devices, and conducting the Site Survey for a host-connected network is the
same as for the standard DX80 wireless system. All device I/O for the network is accessed using the host/master device.
To access the Modbus device, you may first need to configure system-level communication parameters on the DX80 Gateway, in
addition to the serial hookups shown below. The following procedure is necessary to change the Gateway Slave ID, Baud Rate, and
Parity.
Parameter Description
Slave ID (Default = 1)
Defines the slave number (01-99) for the serial Modbus RTU protocol. When operating more than one
network with a Modbus Master device, change the Slave IDs.
Baud Rate (Default = 19200)
Defines communication data rate (19.2, 38.4 or 9.6 kbps) between the Gateway and the Host through the
serial interface.
Parity (Default = None) Defines serial parity (none, even, or odd) between Gateway and Host.
Host Network - Gateway
Brown 1 10-30V dc Input
White 2 RS485 / D1 / B /+
Blue 3 Ground Input
Black 4 RS485 / D0 / A / -
Gray 5 Comms Gnd
Wiring: 5-pin Euro pinouts for 485+, 485- and
Comms ground
Gateway (Host-Connected) Pinout Diagram