Cut Sheet

Environmental Certifications
Operating Conditions
Temperature: 0° to +50°C (+32° to 122°F)
Max. Relative Humidity: 90% @ 50°C (non-condensing)
Design Standards: EN 60947-1, EN 60947-5-1, EN
60068-2-6, EN 60068-2-27
Required Overcurrent Protection
WARNING: Electrical connections must be made
by qualified personnel in accordance with local
and national electrical codes and regulations.
Overcurrent protection is required to be provided by end product
application per the supplied table.
Overcurrent protection may be provided with external fusing or via
Current Limiting, Class 2 Power Supply.
Supply wiring leads < 24 AWG shall not be spliced.
For additional product support, go to http://
www.bannerengineering.com.
Supply Wiring (AWG)
Required Overcurrent Protection (Amps)
20 5.0
22 3.0
24 2.0
26 1.0
28 0.8
30 0.5
Dimensions for IM-T-9A and IM-T-11A
118.0 mm
(4.65")
84.0 mm
(3.31")
22.5 mm
(0.89")
Machine
Safety
IM-T -9A
13
S1 S2 Y1
23 33
K1
K2
Y2
Ch.1
Ch.2
Y3 S3 S4
Y4 14 24 34
Figure 9. Interface module dimensions
IM-T-9A and IM-T-11A Interface Modules
10 www.bannerengineering.com - Tel: +1-763-544-3164 P/N 62822 Rev. F