Manual

- 19 -
ELECTRICAL DATA - 1140 RPM MODELS 60Hz
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
ELECTRICAL DATA - 1140 (950) RPM MODELS 50Hz
M.C.A. = Minimum Circuit Ampacity (AMPS)
M.O.P. = Maximum Overcurrent Protection (AMPS)
NO.
OF
FANS
208-230/3/60 460/3/60 575/3/60
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
1
6.6 8.3 15 3.1 3.9 15 2.5 3.1 15
2
13.2 14.9 20 6.2 7 15 5 5.6 15
3
19.8 21.5 25 9.3 10.1 15 7.5 8.1 15
4
26.4 31 35 12.4 13.2 15 10 10.6 15
5
33 34.7 40 15.5 16.3 20 12.5 13.1 15
6
39.6 46 50 18.6 21 25 15 15.6 20
8
52.8 61 70 24.8 25.6 30 20 20.6 25
10
66 71 80 31 36 40 25 25.6 30
12
79.2 91 100 37.2 41 45 30 36 40
NO.
OF
FANS
200-220/3/50 380-400/3/50
TOTAL
FLA
MCA MOP
TOTAL
FLA
MCA MOP
1
5.9 7.4 15 2.7 3.4 15
2
11.8 13.3 15 5.4 6 15
3
17.7 19.1 25 8.0 8.7 15
4
23.6 25 30 10.7 11.4 15
5
29.5 36 40 13.4 16 20
6
35.3 41 45 16.1 16.8 20
8
47.1 51 60 21.4 26 30
10
58.9 71 80 26.8 31 35
12
70.7 81 90 32.2 36 40