CHAPTER 7: RFID COMMANDS
COBALT HF RFID CONTROLLERS OPERATOR’S MANUAL
P/N: 17-1320 REV 01 (03-06) PAGE 91 OF 116
Continuous Read Mode Evoked - Response from Controller (after Tag Read)
PARAMETER FIELD CONTENT
Header
0x02, 0x02
Response Size
0x0005
Command Echo 0x0D
Data from address 0x0001
0x05
Data from address 0x0002
0xAA
Data from address 0x0003
0xE7
Data from address 0x0004
0x0A
Checksum
Optional
Terminator
0x03
To exit out of Continuous Read mode, issue Command 0D with zero (0x0000) in the
Read Length parameter field.
Stopping Continuous Read - Command from Host
PARAMETER FIELD CONTENT
Header
0x02, 0x02
Command Size
0x0006
Command ID 0x0D
Start Address
0x0001
Read Length
0x0000
Delay Between Duplicate Reads
0x02
Checksum
Optional
Terminator
0x03
Stopping Continuous Read - Response from Controller
PARAMETER FIELD CONTENT
Header
0x02, 0x02
Response Size
0x0001
Command Echo 0x0D
Checksum
Optional
Terminator
0x03