Specifications

16
T
he Enable function is established by
w
iring a switch or contact in series with
t
he orange Main Speed Potentiometer
lead which connects to Terminal “P2”.
When the Enable Switch is closed, the
motor will accelerate to the Main
Speed Potentiometer setting. When
the Enable Switch is opened, the
motor will decelerate to stop.
WARNING! If the Enable
S
witch is to be mounted
remotely, it is highly recommended
t
hat the ID5SI-2 Signal Isolator
be installed.
5.9 Run/Fault Relay Connection – The Run/Fault
Relay Output Contacts are located at TB2 and
can be used to turn on or off equipment or to
signal a warning if the drive is put into the Stop
Mode or a fault has occurred. See Figure 15.
The Run/Fault Relay Contact status for various
drive operating conditions is shown in Table 6.
F
IGURE 14 – ENABLE CIRCUIT CONNECTION
M
ain Speed
P
otentiometer
E
nable Switch or Relay
O
range (Wiper)
V
iolet (High)
W
hite (Low)
(Close to Run)
P1P2P3
FIGURE 15 – RUN/FAULT RELAY OUTPUT
CONTACTS CONNECTION
Output Contacts
Run/Fault Relay
Normally Closed
Relay Common
Normally Open
NCNO
TB2
COM
6 SETTING SELECTABLE
JUMPERS
The drive has customer selec-
table jumpers which must be set
before the drive can be used.
For the location of jumpers, see
Figure 2, on page 9.
Note: Disconnect the AC line
before changing position of
jumpers.
6.1
LINE INPUT VOL
T
AGE
SELECTION (J1
(CATALOG NOS. ID5601,
ID5602)) –
Jumper J1 is factory installed on Terminal “230V” for 208/230 Volt AC line input. For 115
Volt AC line input, the jumper must be removed and installed on Terminal “115V”. See Figure 16.
Drive
Operating
Condition
Description
Run Relay Operation
(Jumper J8 Installed in “R” Position)
(Factory Setting)
Fault Relay Operation
(Jumper J8 Installed in “F” Position)
Normally
Open Contact
Normally
Closed Contact
Normally
Open Contact
Normally
Closed Contact
Power Off Main Power Disconnected Open Closed Open Closed
Run Mode* Normal Drive Operation Closed Open Closed Open
Stop Mode* Selected by Operator Open Closed Closed Open
Fault** Drive Tripped Open Closed Open Closed
TABLE 6 – DRIVE OPERATING CONDITION AND RUN/FAULT RELAY CONTACT STATUS
*Run Mode or Stop Mode is selected using the Start/Stop Switch. **Overload, I
2
t, Short Circuit, Undervoltage, Overvoltage.
FIGURE 16 – CATALOG Nos. ID5601*, ID5602 AC LINE INPUT VOLTAGE SELECTION
208/230 Volt AC Line Input
(Factory Setting)
(J1 Installed on Terminal “230V”)
115 Volt AC Line Input
(J1 Installed on Terminal “115V”)
115V
J1
230V
J1
115V 230V
*La
yout of Ca
talog No.
ID5601 varies slightl
y
.