Specifications

5.1 AC LINE INPUT CONNECTION – Wire
the AC line input to Terminal Block TB1.
GFCI Operation – Do not connect
this drive to an AC power source
controlled by a Ground Fault Circuit
Interrupter. Special software is avail-
able for GFCI operation – contact
your local Baldor District Of
fice.
Note: The rated AC line voltage of the
drive must match the actual AC line
input voltage. On Catalog Nos. ID5601,
ID5602, the setting of Jumper J1 must
match the AC line input voltage.
Catalog Nos. ID5601, ID5602:
Designed to accept single-phase (Terminals “L1”, “L2”) AC line input only. Rated for 208/230 Volt AC
line input with Jumper J1 set to the “230V” position (factory setting). Rated for 115 Volt AC line input
with Jumper J1 set to the “115V” position. See Figure 7.
5 WIRING INSTRUCTIONS
W
ARNING! Read Safety Warning, on page 5, before using the drive. Disconnect main
p
ower before making connections to the drive. To avoid electric shock, be sure to
p
roperly ground the drive. It is highly recommended that the ID5SI-2 Signal Isolator be installed
w
hen using signal following.
A
pplication Note – To avoid erratic operation, do not bundle the AC line and motor wires with each
o
ther or with wires from signal following, start/stop contacts, or any other signal wires. Also, do not
b
undle motor wires from multiple drives in the same conduit. Use shielded cables on all signal wiring
o
ver 12” (30 cm). The shield should be earth grounded on the drive side only. Wire the drive in
accordance with the National Electrical Code requirements and other local codes that may apply.
Be sure to properly fuse each AC line conductor that is not at ground potential. Do not fuse neutral
o
r grounded conductors. A separate AC line switch or contactor must be wired as a disconnect so
that each ungrounded conductor is opened. For fuse or circuit breaker selection, see Table 5. Also
see Section 10, on page 21.
To maintain the watertight integrity of the drive, be sure to use suitable watertight connectors and
wiring which are appropriate for the application. Catalog No. ID5601 contains two mounting holes
for standard 1/2” liquidtight fittings (not supplied) (one watertight plug is provided, if only one knock-
out is used). Catalog Nos. ID5602, ID5203, ID5403, ID5405 contain two mounting holes for standard
1/2” liquidtight fittings (not supplied) and one mounting hole for standard 3/4” liquidtight fitting (not
supplied) (two watertight plugs are provided, if only one knockout is used).
The drive is designed with a hinged case so that when the front cover is open, all wiring stays intact.
To open the cover, the four screws must be loosened so they are no longer engaged in the case
bottom. After mounting and wiring, close the cover making sure that the wires do not get caught or
crimped as the cover is closed. Tighten the four screws so that the gasket is slightly compressed.
The recommended tightening torque is 12 in-lbs (14 kg-cm). See Figures 3 and 4, on page 11, for the
tightening sequence. Do not overtighten.
13
Terminal
Block Description Catalog No.
Maximum Wire Size (Cu) Recommended Tightening Torque
AWG
mm
2
in-lbs kg-cm
TB1 AC Line Input and Motor Wiring
ID5601 12 3.3 7 8
ID5602, ID5203, ID5403, ID5405 12 3.3 12 14
TB2 Run/Fault Relay Output Contacts All 16 1.3 3.5 3
TABLE 5 – TERMINAL BLOCK WIRING INFORMATION
FIGURE 7 – CATALOG Nos. ID5601, ID5602*
AC LINE INPUT, MOTOR, AND GROUND CONNECTIONS
AC LINEMOTOR
Motor
VUW
AC Line Input
115, 208/230 Volt
Single-Phase Ground (Earth)
L1 L2
TB1
*Ca
talog No. ID5602 is rated 1
1
2 HP maximum with 115
Volt AC line input and
2 HP maximum with 208/230
V
olt
AC line input.