Specifications
MN715P General Information 2-3
WARNING: Motor circuit may have high voltage present
whenever AC power is applied, even when motor is not rotating.
Electrical shock can cause serious or fatal injury.
WARNING: Dynamic brake resistors may generate enough heat
to ignite combustible materials. Keep all combustible materials
and flammable vapors away from brake resistors.
Caution: Disconnect motor leads (T1, T2 and T3) from control
before you perform a “Megger” test on the motor. Failure to
disconnect motor from the control will result in extensive
damage to the control. The control is tested at the factory for
high voltage / leakage resistance as part of Underwriters
Laboratories Inc. requirements.
Caution: Do not connect AC power to the Motor terminals T1, T2
and T3. Connecting AC power to these terminals may result in
damage to the control.
Caution: Baldor recommends not using “Grounded Leg Delta”
transformer power leads that may create ground loops. Instead,
we recommend using a four wire Wye.