Specifications

MN715P Setup and Operation 4-3
S1 Settings Continued
Switch Setting Description
1
OFF Base Frequency = 60Hz
1
ON Base Frequency = 50Hz
OFF Maximum frequency limit = Base Frequency (60/50Hz)
2
ON Maximum frequency limit = 2 X Base Frequency (130
or 110 Hz)
3
OFF Reverse motor rotation ENABLED
3
ON Does not allow reverse motor rotation
OFF Power up Start DISABLED (see notes)
4
ON Power up Start ENABLED the control will resume
operation as soon as power is applied. Power up start
is disabled the first time you power up the drive (see
notes).
5
OFF Terminal 2 wire mode (If S1-8 = ON)
5
ON Terminal 3 wire mode (If S1-8 = ON)
6
OFF Analog input VOLTAGE (if S1-7 = ON)
6
ON Analog input CURRENT (if S1-7 = ON)
7
OFF Use local speed reference (front panel potentiometer)
7
ON Use remote speed reference (J4 connector)
8
OFF Use local commands (front panel FWD, REV, STOP)
8
ON Use remote commands (J4 connector)
Note 1: If power up start is ON and local commands are used, the drive will
resume operation in the same FWD or REV direction when power is
applied.
Note 2: If power up start is ON and remote 2 wire commands are used, the
drive will resume operation if the forward or reverse switch is still
closed (2 wire).
Note 2: If power up start is ON and remote 3 wire commands are used, the
drive will not allow power up start operation (unless the momentary
contacts stop and forward or reverse are manually held closed
during power up).
Note 4: After power down, if any S1 switch position is changed, power up
start is cancelled.