Specifications

3-10 Receiving and Installation MN715P
Digital Inputs
(S1-8 = OFF)
If S1-8 is OFF, the front panel commands FWD, REV and STOP are
selected. The J4 inputs are ignored.
(S1-8 = ON)
Three inputs are available on the J4 connector. Switch S1-5 determines
whether two wire or three wire operation is used. If two wire is selected
(S1-5= OFF) the STOP input at J4-6 is not used.
Note: Pressing the STOP switch on the front panel keypad will override the
J4 commands and cause the motor to decel to a stop.
2 Wire Operation of Digital Inputs (S1-5 = OFF)
J4
4
5
6
Reverse
Not Used
Forward
J4-4 Forward
Open – Disables forward operation.
Decel to stop.
Closed – Starts forward motor rotation.
J4-5 Reverse
Open – Disables reverse operation.
Decel to stop.
Closed – Starts reverse motor rotation.
1
GND
3 Wire Operation of Digital Inputs (S1-5 = ON)
J4
1
4
5
6
Reverse
Stop
Forward
GND
J4-4 Forward
Momentary Closed – Starts forward
motor rotation.
J4-5 Reverse
Momentary Closed – Starts reverse
motor rotation.
J4-6 Stop
Momentary Open – Motor decels to
stop.
Note: Simultaneous closure of J4-4 and J4-5 will cause the motor to decel
to stop if the motor is running. If the control is in a fault condition,
simultaneous closure of these inputs will attempt a fault reset.