User manual
6 Modbus RTU MN744
Table 4 Coil Table Continued
Modbus Ref Coils
Class Location Description (When Set)
00066 VIS Control Command Bit 1 FAULT RESET - 0 write has no effect other than to clear the coil. A write of 1 issues a
drive-reset request and attempts to clear all active fault conditions. If successful, operation
resumes at previous command. Ignored if no fault is active.
Note: maximum number of resets/hour is limited. See user manual details.
00067 VIS Control Command Bit 2 CLEAR FAULT LOG - positive edge clears the fault log.
00068 VIS Control Command Bit 3 CLEAR ALL - positive edge clears the fault log and loads factory default parameters into the
drive. Drive must be disabled to execute this command.
00069 VIS Control Command Bit 4 RESTORE FACTORY SETTINGS - positive edge resets all parameters to the initial factory
condition in the active parameter table. Drive must be disabled.
00070 VS Control Command Bit 5 CALCULATE MOTOR MODEL PARAMETERS - positive edge causes calculation motor
parameters. Drive must be disabled to perform this operation.
00071 VS Control Command Bit 6 CALCULATE PRESETS - positive edge causes a calculation of initial values for tuning and
performance parameters based on motor nameplate values. Drive must be disabled to perform
this operation.
00074 VIS Control Command Bit 9 CLEAR POSITION COUNTER - positive edge zeros the position counter
00076 VIS Control Command Bit 11 RESET OPTION CARD 1 - positive edge resets option card 1. If option card is not installed no
action is taken
00077 VIS Control Command Bit 12 RESET OPTION CARD 2 - positive edge resets option card 2. If option card is not installed no
action is taken
00078 VIS Control Command Bit 13 STOP COMMAND - level sensitive, 1 causes the drive to STOP and DISABLE, 0 has no effect.
Operating Mode Parameter, P1401, must be set to NETWORK. This input overrides
FORWARD, REVERSE and BIPOLAR coils.
00079 VIS Control Command Bit 14 FORWARD COMMAND - level sensitive, 1 causes the drive to run FORWARD, 0 causes the
drive to STOP. Operating Mode Parameter, P1401, must be set to NETWORK and forward
enable on J2 must be 1.
00080 VIS Control Command Bit 15 REVERSE COMMAND - level sensitive, 1 causes the drive to run REVERSE, 0 causes the
drive to STOP. Operating Mode Parameter, P1401, must be set to NETWORK and reverse
enable on J2 must be 1.
00081 VIS Control Command Bit 16 BIPOLAR COMMAND - level sensitive, 1 allows the drive to run in FORWARD or REVERSE, 0
causes the drive to STOP. Operating Mode Parameter, P1401, must be set to NETWORK and
forward & reverse enables on J2 must be 1.
00082 VIS Control Command Bit 17 DRIVE ENABLE - level sensitive, 1 enables drive, 0 disables drive. Operating Mode Parameter,
P1401, must be set to NETWORK and drive enable on J2 must be 1.
00083 VIS Control Command Bit 18 Positive Edge Invokes Next Autotuning Test. Will have same action as Command Bits 19 if no
more tests in sequence.
00084 VIS Control Command Bit 19 Positive Edge Ends Autotuning Test Sequence without invoking next test.
00085 VIS Control Command Bit 20 Positive Edge Aborts ongoing Auto-tune test.
00088
00096
Control Command Bits 23-31 Coils 88 through 96 are reserved
00097 VIS Control Card Output 1 - digital, read any time, write in network mode only
00098 VIS Control Card Output 2 - digital, read any time, write in network mode only
00099 VIS Control Card Output 3 - relay, read any time, write in network mode only
00100 VIS Control Card Output 4 - relay, read any time, write in network mode only
00101 VIS Option Card 1 Output 5 - read any time, write in network mode only
00102 VIS Option Card 1 Output 6 - read any time, write in network mode only
00103 VIS Option Card 2 Output 7 - read any time, write in network mode only
00104 VIS Option Card 2 Output 8 - read any time, write in network mode only
00105
00108
Reserved Reserved