Specifications

DESIGN SPECIFICATIONS
Microprocessor controlled PWM output
Output frequency 0.25-120Hz, optional 0.25-400Hz
Peak overload capacity of 200%
Process follower 0-5VDC, 0-10VDC, 4-20mA
Free run or ramp stop
Controlled reversing
Selectable preset speeds
Jog speed
Dynamic braking
DC Injection braking
Separate accel/decel rates
PID-Setpoint control
Bus present and fault trip LED
Fault trip output for customer use
2 Programmable analog meter outputs
4 Programmable Opto outputs
NEMA 1 enclosure as standard (-E, -EO) 1-800 hp
NEMA 4X enclosure as standard(-W) 1-20 hp
ENVIRONMENTAL AND
OPERATING CONDITIONS
Input voltage - 1 or 3 phase 200-240
VAC±10%, 3 phase 380-480 VAC ±10%, 3 phase 550-600
VAC ± 10%
Input frequency - 50 or 60Hz ±5%
Service factor - 1.0
Duty - continuous
Humidity - 90% max RH non-condensing
Altitude - 3300 feet max without derate
OPERATOR KEYPAD
Digital speed control
Forward command
Reverse command
Stop command
Jog speed
Display 32 character alpha-numeric
Local/Remote key
Remote mount to 100 feet
Membrane keys with tactile feel
NEMA 4X enclosure
PROTECTIVE FEATURES
Selectable automatic restart at
momentary power loss with free
setting of maximum number of trips
and time between trip and reset
DC bus charge indicator
Adjustable time-base overload
Cause of last 31 trips retained in memory
Linear heat sink thermal sensor
Digital display for fault conditions including:
- Over voltage
- Under voltage
- Over current
- Ground fault
- Drive overload
- Heatsink thermal
- External trip
Output Overload 150% for 60 seconds, 170-200% for 3 seconds constant torque
Ratings Capacity 115% for 60 seconds for variable torque
Frequency 0-400Hz
Voltage 0-Maximum Input Voltage (RMS)
Input Frequency 50 Hz 60 Hz
Ratings Voltage 180-230 VAC 340-457 VAC 180-264 VAC 340-528 VAC 495-660 VAC
Phase Three Phase or Single Phase with derate
Control Impedance 1% minimum for required for sizes B2, C2, D2, F, G, G2, G+; 3% minimum for sizes A, E
Spec Method Sinewave Carrier Input, PWM Output
Speed Setting ±5vdc, 0-5vdc, ±10vdc, 0-10vdc, 4-20mA, Digital via Keypad, RS-232, RS-485, DeviceNet, Modbus Plus, Profibus
Accel/Decel 0-3600 Seconds linear or S-curve to maximum speed
Dynamic Braking 20% Min on E,W models, EO models require optional external assemblies
LCD Setup Parameter values for setup and review
Display Running Motor RPM, output current, output voltage, local remote control, Fwd/Rev
Faults Separate message for each trip, last 31 retained in memory
Diagnostics Review of setup and operating parameters
Ambient Temperature 0-40 Deg C for UL listing
Conditions Cooling Forced air included when required
Altitude 0-3300 feet without derate
Humidity 0-90% Max RH non-condensing for NEMA 1; 100% condensing for NEMA 4
7