Installation guide

Software Setup 5-7
Standard Series H Area Register Mapping Continued
Register
Address
T# Read/Write Description
49000
1 Read/Write Run Cmd (0=stop, 1=fwd, 2=rev, 3=bipolar)
49001 2 Write Only Run Inhibit (1=stop, regardless of Control
Source)
49002 3 Read/Write Control Source (0=keypad,1=terminal
strip,2=network)
49003 5 Read/Write Command Mode (see NOTE 2)
49004 4 Read Only Control State (0=not ready, 1=ready, 2=enabled,
3=stopping, 4=faulted
49005 45 Read Only Fault Status (0=no fault present)
49006 46 Write Only Fault Reset (1=execute fault reset)
49007 49 Write Only Force Fault (01=force network fault)
49008 50 Read Only Security Status (0=disabled, 1=unlocked,
2=locked)
49009 51 Write Only Security Lock (valid code unlocks, any other
locks)
49010 39 Read/Write Table Select (parameter table select 03)
49011 40 Read/Write Acc/Dec Group (12)
49012 41 Read/Write Watchdog Time (0=disable) (10 ms minimum
for vector) (1 sec. minimum for inverter)
(see NOTE 3)
Note:
To use register 49000, you must jumper terminals J18, J19,
J110 and J117 together to allow the motor to run.