Installation guide

5-4 Software Setup
For 15Hand 21H Inverter controls, use the following registers for
communication. For all other H controls, use the Standard Series H
Area Register Mapping.
Series 15H Specific Area Register Mapping
Register
Address
T# Read/Write Description
47000 31 Read Only Terminal Strip (see NOTE 1)
47001 45 Read Only Fault Status (0=no fault present)
47002 17 Read Only Current Actual (100mA RMS)
47003 18 Read Only Speed Actual (RPM)
47004 19 Read Only Frequency Actual (.1 Hz)
47005 33 Read Only Software Revision (ex S154.03 is returned as 403)
47006 34 Read Only Product Series (ex Series 15H returns 15)
47007 35 Read Only Product Class (5=H)
47008
1 Read/Write Run Cmd (0=stop, 1=fwd, 2=rev, 3=bipolar)
47009 5 Read/Write Command Mode (see NOTE 2)
47010 6 Read/Write Hz Speed Ref
47011 3 Read/Write Control Source (0=keypad, 1=terminal strip, 2=net-
work)
47012 Reserved
47013 75 Write Only Digital Output
47014 46 Write Only Fault Reset (1=execute fault reset)
Notes:
After the fault is cleared (1=execute fault reset), you must send a
stop (run cmd=0) followed by the direction for the run command
again. Otherwise, the motor will not run.
To use register 47008, you must jumper terminals J48, J49,
J410 and J417 together to allow the motor to run.