Specifications
4-3 Setup and Operation MN715P
S1 Settings Continued
Switch
Setting Description
OFF Base Frequency = 60Hz
1
ON Base Frequency = 50Hz
OFF Maximum frequency limit = Base Frequency (60/50Hz)
2
ON Maximum frequency limit = 2 X Base Frequency (130 or 110 Hz)
OFF Reverse motor rotation ENABLED
3
ON Does not allow reverse motor rotation
OFF Power up Start DISABLED (see notes)
4
ON Power up Start ENABLED the control will resume operation as soon
as power is applied. Power up start is disabled the first time you
power up the drive (see notes).
OFF Terminal 2 wire mode (If S1-8 = ON)
5
ON Terminal 3 wire mode (If S1-8 = ON)
OFF Analog input VOLTAGE (if S1-7 = ON)
6
ON Analog input CURRENT (if S1-7 = ON)
OFF Use local speed reference (front panel potentiometer)
7
ON Use remote speed reference (J4 connector)
OFF Use local commands (front panel FWD, REV, STOP)
8
ON Use remote commands (J4 connector)
Note 1: If power up start is ON and local commands are used, the drive will resume
operation in the same FWD or REV direction when power is applied.
Note 2: If power up start is ON and remote 2 wire commands are used, the drive will
resume operation if the forward or reverse switch is still closed (2 wire).
Note 3: If power up start is ON and remote 3 wire commands are used, the drive will
not allow power up start operation (unless the momentary contacts stop and
forward or reverse are manually held closed during power up).
Note 4: After power down, if any S1 switch position is changed, power up start is
cancelled.










