REVOLUTION SYSTEM OVERVIEW MANUAL 1 Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Transforming the Control of Hot Tubs Revolution Intellectual Property Advisement All Intellectual property, as defined below, owned by or which is otherwise the property of Balboa Water Group or its respective suppliers relating to the Balboa Water Group Revolution Spa Control, including but not limited to, accessories, parts, or software relating there to (the “System”), is proprietary to Balboa Water Group and protected under federal laws, state laws, and international treaty provisions.
Transforming the Control of Hot Tubs Revolution Warnings: Danger! Risk of Electric Shock! 3 t All electrical work must be performed by a qualified electrician and must conform to all national, state, and local codes. t Before making any electrical connections, make certain that the Main Power breaker from the house breaker box has been turned off. t Do not attempt service of this control system. Contact your dealer or service organization for assistance.
Transforming the Control of Hot Tubs Revolution CAUTION Test the ground fault circuit interrupter before each use of the spa. Read the instruction manual. Adequate drainage must be provided if the equipment is to be installed in a pit. To ensure continued protection against shock hazard, use only identical replacement parts when servicing. t Install a VG Compliant suction guard that is suitably rated to match the maximum flow rate marked.
Transforming the Control of Hot Tubs Revolution GFCI It is required by code to install a Ground Fault Circuit Interrupter (GFCI) in the supply power for a spa. This device will trip the breaker if there is an unsafe electrical condition caused by a malfunctioning component or even the slightest short to ground. Note: Connect the control system only to a circuit protected by a Class A GFCI mounted at least 5’ (1.
TABLE OF CONTENTS REVOLUTION OVERVIEW 7 SPA BEHAVIOR 37 Revolution Features . . . . . . . . . . . . . .9 Pumps, Operation . . . . . . . . . . . . . 38 Revolution Specifications . . . . . . . . . . . 10 Circulation Pump Modes . . . . . . . . . . . 40 Revolution Components . . . . . . . . . . . 11 Filtration and Ozone . . . . . . . . . . . . . 40 System Dimensions . . . . . . . . . . . . . .12 Freeze Protection . . . . . . . . . . . . . . 41 13 Clean-up Cycle (optional) . . . . . . . . . . .
Revolution Overview 7 Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Overview REVOLUTION – Transforming the Control of Hot Tubs Balboa’s Revolution hot tub control is setting a new industry standard for unmatched system reliability, manufacturing flexibility and end user friendliness. INCOMPARABLE SYSTEM RELIABILITY Utilizing advanced technology and high temperature corrosion proof mission critical materials from the automotive and other industries, the Revolution hot tub control systems all but eliminate leaks due to corrosion or harsh chemicals.
revolution features MANUFACTURED UNDER ONE OR MORE OF THESE PATENTS: U.S. PATENTS: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417,834 B2, CANADIAN PATENT: 2342614, AUSTRILIAN PATENT: 2373248 OTHER PATENTS BOTH FOREIGN AND DOMESTIC APPLIED FOR AND PENDING. ALL SOFTWARE COPYRIGHT BALBOA WATER GROUP.
Transforming the Control of Hot Tubs TP600 Panel Revolution Revolution Specifications System Model Revolution 60 Hz (BP1500), 50 Hz (BP1600) Part Numbers TP400 Series Panel BP1500 (60Hz): 56125-02 4kW 800 Incoloy Element 56126-02 With 4kW Titanium Element BP1600 (50Hz): 56129-02 3kW 800 Incoloy Element 56130-02 3kW Titanium Element Topside Panels TP600 Panel AX10: One button TP400 Series Panel AX20: Two button TP400T (Temp, Jets, Light, Aux) AX40: Four button TP400W (Warm, Cool, Light, Jets) Coup
Transforming the Control of Hot Tubs Revolution Revolution Components 1 2 2 4 5 6 11 5 3 1 Electric Housing Cover 2 Bi-directional Flow Heater 3 Heater Housing 4 Electronic Enclosure 5 Nut and Tailpiece 6 Support Legs 6 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution System Dimensions 5.2” 4.4” 8.5” 18.4” FRONT VIEW with tail pieces 5.8” SIDE VIEW (RIGHT SIDE) 11.45” 3.47” 5.30” 15.0” FRONT VIEW w/o tail pieces 12 BOTTOM VIEW Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Menus and Panel Operation 13 Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Transforming the Control of Hot Tubs Revolution Menus & Panel Operation TP PANEL SERIES READY JETS J S TP600 RANGE FLTR1 AUX UX X LIGHT LIGHT HEAT HEAT AT All TP panels shown on this page work with both Revolution models BP1500 and BP1600 models. They all have capabilities for navigation, setting functions and modes (time, temperature, filter cycles, preferences), sensor related messages, reminder messages, diagnostic messages, and utilites such as fault logs. .
Transforming the Control of Hot Tubs Revolution Panel Navigation Navigating the entire menu can be accomplished with two buttons: 1) Either temperature button (also, if the panel has a single TEMP icon) 2) The Light button NOTE: Hereafter, all temperature buttons (i.e., “Warm” and “Cool”) will be referred to as a TEMP button.
Transforming the Control of Hot Tubs Revolution Main Menu -- Revolution TP Series Control Panels Main Menu t TEMP t MODE t TIME t FLIP t LOCK LOCK t HOLD HOLD t FILTER No. 1 FILT1 t FILTER No. 2 t LITE TIMR * t PREF t UTIL TEMP MODE TIME FLIP FILT2 PREF UTIL * LITE TIMR — This menu item may or may not appear depending on a manufacturer’s configuration. 16 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Temperature Adjustment t Press TEMP buttons for desired set temperature. t The numbers flash during temperature adjustment. t Press LIGHT to return to main menu; or, main screen returns in 5 seconds. Temperature Adjustment with One TEMP Button on Panel. Press TEMP buttons for desired set temperature. t 1st TEMP button press causes temperature to flash. t 2nd TEMP button press causes the temperature to change.
Transforming the Control of Hot Tubs Revolution Dual Temperature Ranges READY RANGE FLTR High Range Arrow READY RANGE FLTR1 Low Range Arrow The water temperature display will show whether the system is in High or Low Range. 18 The Revolution system incorporates two temperature range settings that allows an independent set temperature within each range. The High Range is designated in the display by an “up” arrow, and the Low Range is designated in the display by a “down” arrow.
Transforming the Control of Hot Tubs Revolution Dual Temperature Ranges (cont.) READY JETS J S Setting a High Temperature Range RANGE FLTR1 AUX UX LIGHT LIG HEAT HEAT AT T From the Main Screen, press TEMP to view current set temperature RANGE SET JETS J S RANGE AUX UX X LIGHT LIG G SET HEAT ATT is displayed for the High Range RANGE SET JETS J S AUX UX X LIGHT LIG Press TEMP to set desired temperature. SET HEAT ATT Press LIGHT to exit.
Transforming the Control of Hot Tubs Revolution Dual Temperature Ranges (cont.) READY JETS J S Setting a Low Temperature Range RANGE FLTR1 AUX UX LIGHT LLIG GHT HEAT HEAT AT T From the Main Screen, press TEMP to view current set temperature RANGE SET JETS J S AUX UX X RANGE SET JETS J S 20 SET HEAT ATT is displayed RANGE RANGE LIGHT LIG IGHTT AUX UX LIGHT LIG SET HEAT HEAT ATT is displayed Press TEMP to Toggle Range Arrow Up or Down Manufactured under one or more of these patents. U.
Transforming the Control of Hot Tubs Revolution Dual Temperature Ranges (cont.) JETS J S RANGE AUX UX X LIGHT LIG HEAT HEAT ATT is displayed for Low Range GE FLTR1 Press LIGHT to Exit to Low Range Temperature Menu Press LIGHT to Exit to Low Range Temperature Menu AUX X LIGHT LIG HEAT ATT is displayed for Low Range Press TEMP to set desired temperature. Exiting reverts the display back to the main screen. RANGE FLTR1 SET JETS J S Press TEMP to set a low temperature set point.
Transforming the Control of Hot Tubs Revolution Spa Light READY JETS J TS S 22 RANGE FLTR1 AUX AUX LIGHT LIGH LIG IGHT T HEAT HEAT AT T The Light button turns the spa light on and off. Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending.
Transforming the Control of Hot Tubs Revolution Mode -- Ready and Rest In order for the spa to heat, a pump needs to circulate water through the heater. The pump that performs this function is known as the “heater pump.” RANGE FLTR1 READY JETS J S AUX UX LIGHT LLIG GHT The heater pump can be either a 2-Speed Pump 1 or a circulation pump.
Transforming the Control of Hot Tubs Revolution Mode -- Ready and Rest (cont.) Ready Mode t READY Mode will allow the spa to Poll and determine a need for heat. The panel will maintain a “current” temperature display. Rest Mode REST RANGE FLTR1 REST RANGE After one hour... REST RANGE REST RANGE REST RANGE t REST Mode will not Poll and will only heat during filter cycles. The panel will not display a current temperature at all times.
Transforming the Control of Hot Tubs Revolution Choosing between Ready and Rest Mode READY JETS J S Press TEMP. RANGE FLTR1 AUX UX LIGHT LIG HEAT HEAT T Press TEMP READY JETS J S AUX UX RANGE FLTR1 LIGHT LIG HEAT HEAT ATT The temperature flashes. 25 Press LIGHT repeatedly for MODE Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Choosing between Ready and Rest Mode (cont.) SET READY JETS J S AUX UX X SET LIGHT LLIG IGHT T HEAT HEAT ATT JETS J S In MODE, TEMP button toggles between SET READY and SET REST. REST AUX UX LIGHT LIGH IGHT T HEAT HEAT AT T Choose SET READY or SET REST, then press LIGHT to set and exit.
Transforming the Control of Hot Tubs Revolution HOLD (Standby) Hold Mode is used to disable the pumps during service functions like cleaning or replacing the filter. RANGE SET JETS J S AUX AUX LIGHT LIG T SET HEAT HEAT AT Press TEMP to desired hold temperature Main Screen RANGE SET JETS J S AUX UX LIGHT LIG SET HEAT ATT Press LIGHT repeatedly to HOLD The clock will count down from 60 minutes.
Transforming the Control of Hot Tubs Revolution HOLD (Standby, cont.) Drain Mode (if available) SET JETS J S AUX UX LIGHT LIG HEAT HEATT Some spas have a special feature that allows a pump to be employed when draining the water. When available, this feature is a component of Hold Mode. t Some spas will allow PUMPING OUT (Drain Mode) with JET 1 button. t Press JETS Button for Pump Out/Drain, only if Drain Mode is enabled. t Jet 1 will toggle pump on and off.
Transforming the Control of Hot Tubs Revolution LOCK (Restricting Panel Operation) Locking the panel prevents the spa from being used; it also prevents unwanted temperature adjustments. RANGE SET JETS J S AUX AUX LIGHT LLIG IGHT T SET Main Menu > LOCK HEAT HEAT AT Press TEMP NOTE: Main Screen JETS J S AUX UX LIGHT LIG All automatic functions are still active.
Transforming the Control of Hot Tubs Revolution LOCK (Restricting Operation, cont.
Transforming the Control of Hot Tubs Revolution UNLK (Unlock, Allowing Panel Operation) This Unlock sequence may be used from any screen that may be displayed on a restricted panel. RANGE SET JETS J S AUX UX LIGHT LIG SET Press TEMP. LOCK appears. HEAT HEATT Press TEMP Press and hold TEMP while pressing LIGHT twice. SET JETS J S JETS J S 31 AUX UX AUX UX LIGHT LIG T LIGHT LIG HEAT HEATT HEAT HEATT UNLK screen appears, and then will exit to Main Screen in approx. 3 seconds.
Transforming the Control of Hot Tubs Revolution FLIP Inverts Display. READY JETS J S RANGE FLTR1 AUX UX LIGHT LIG T RANGE FLTR1 32 AUX UX READY JETS J S HEAT AT T LIGHT LIG G HEAT HEAT AT T Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending.
Transforming the Control of Hot Tubs Revolution Setting the 24 Hour Clock This action changes a 12 hour clock to a 24 hour clock. Main > PREF > 24-12 READY JETS J TS S AUX UX X READY JETS J TS S AUX UX RANGE FLTR1 LIGHT LIGH IGHT T HEAT HEAT AT T 33 AUX AUX Press TEMP to initiate a flashing display. t When the temperature flashes, press LIGHT repeatedly until PREF appears. t Press TEMP at PREF RANGE FLTR1 LIGHT LIG GH HEAT HEAT ATT The temperature flashes.
Transforming the Control of Hot Tubs Revolution Setting the 24 Hour Clock (cont.) SET JETS J TS S AUX X LIGHT LIGH IG T IGHT HEAT HEAT AT t Press LIGHT at F/C menu. t Press TEMP to toggle between 24 and 12 hour. t Press LIGHT to 1) enter choice, 2) again to exit PREF menu, 3) again to exit UTIL menu and return to main menu. S JETS J S AUX A X LIGHT LLIG IGHT T HEAT HEAT A AT Toggle between 12 And 24 Hour Press LIGHT to exit. 34 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Temperature Display (F/C) Provides the option to choose between Fahrenheit & Celsius. Main Menu > PREF > F/C READY JETS J TS S AUX A X RANGE FLTR1 LIGHT LLIG IGHT T HEAT HEAT AT T To choose between Fahrenheit and Celsius, toggle between F & C in PREF menu. Press LIGHT to exit. READY JETS J TS S AUX X RANGE FLTR1 LIGHT LIGH IG T IGHT HEAT HEAT ATT The temperature flashes.
Transforming the Control of Hot Tubs Revolution Temperature Display (F/C, cont.) JETS J TS S AUX AUX LIGHT LIG T HEAT AT Press TEMP to toggle choice or SET or SET JETS J S SET AUX AUX LIGHT LLIG GHTT HEAT HEATT JETS J S SET AUX AUX LIGHT LLIG GHTT HEAT HEAT ATT Press Light two more times to exit to main menu. or JETS J TS S AUX X LIGHT LIGH LIG IGHT HEAT AT Press LIGHT to exit to menu 36 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Spa Behavior 37 Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Transforming the Control of Hot Tubs Revolution Pumps, Operation Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low and high speeds if equipped. If left running, the pump will turn off after a time-out period. READY JETS J TS S AUX AUX RANGE FLTR1 LIGHT LIG IGHT GHT HEAT HEAT AT T t The pump 1 low speed will time out after 30 minutes. t The high speed will time out after 15 minutes.
Transforming the Control of Hot Tubs Revolution Pumps, Operation (cont.) Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low and high speeds if equipped. If left running, the pump will turn off after a time-out period. READY JETS J S 39 AUX UX RANGE FLTR1 LIGHT LIGH IGHT T HEAT HEAT AT T t The pump 1 low speed will time out after 30 minutes. t The high speed will time out after 15 minutes.
Transforming the Control of Hot Tubs Revolution Circulation Pump Modes If the system is equipped with a circ pump, it may be configured to work in one of three different ways: READY JETS J TS S AUX AUX t The circ pump operates continuously (24 hours) with the exception of turning off for 30 minutes at a time when the water temperature reaches 3°F (1.5°C) above the set temperature (most likely to happen in very hot climates). t The circ pump stays on continuously, regardless of water temperature.
Transforming the Control of Hot Tubs Revolution Freeze Protection If the temperature sensors within the heater detect a low enough temperature, then the pump(s) and the blower automatically activate to provide freeze protection. The pump(s) and blower will run either continuously or periodically depending on conditions. In colder climates, an optional additional freeze sensor may be added to protect against freeze conditions that may not be sensed by the standard sensors.
Transforming the Control of Hot Tubs Revolution System Default Operation Settings PUMPS READY JETS J TS S AUX UX RANGE FLTR1 LIGHT LIGH IG T IGHT HEAT HEAT AT T Press the “Jets 1” button once to turn pump 1 on or off, and to shift between low and high speeds if equipped. If left running, the pump will turn off after a time-out period. t The pump 1 low speed will time out after 30 minutes. t The high speed will time out after 15 minutes.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration FILT1: Main Filtration READY JETS J TS S AUX A X RANGE FLTR1 LIGHT LLIG IGHT T HEAT HEAT AT T Filter cycles are set using a start time and a duration. Start time is indicated by an “A” or “P” in the bottom right corner of the display. Duration has no “A” or “P” indication. Each setting can be adjusted in 15-minute increments. The panel calculates the end time and displays it automatically.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F1 In adjusting the filtration times, you’ll enter Filtration Screen one (F1), set the beginning time (in hours and minutes), and then the duration. The second filtration times (F2) are created the same way. Main Menu > FILT1 > OFF/ON > BEGN At the main screen, begin by pressing TEMP.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F1 (cont.) Press TEMP to advance to the beginning of the time setting process for filtration. 1 JETS J S AUX AUX LIGHT LIGH IGHT G T HEAT HEAT A AT FLTR1 flashes TEMP advances to the first screen to change time for F1. (BEGN will appear, which stands for begin.) FLTR1 JETS J S AUX X LIGHT LIG JETS J S AUX AUX LIGHT LIGH IGHT T FLTR1 SET 45 HEAT AT P The hour will flash. Press TEMP to change the hour.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F1 (cont.) SET FLTR1 JETS J TS S AUX AUX LIGHT LLIG IGHT T FLTR1 SET JETS J TS S AUX UX X LIGHT LIGH IGHT T JETS J TS S AUX AUX LIGHT LIG T SET 46 P Press LIGHT to advance to minutes. HEAT HEAT AT T P Press TEMP to change minutes. HEAT HEAT AT FLTR1 P Press LIGHT to set Run Hours. HEAT HEAT AT T Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F1 (cont.) FLTR1 JETS J S AUX X LIGHT LIGHT FLTR1 HEAT ATT JETS J TS AUX X LIGHT LIGH Press TEMP to begin hour change for F1. HEAT AT T Each TEMP press increments the hours. FLTR1 SET JETS J TS AUX AUX SET HEAT HEAT AT T FLTR1 JETS J TS S 47 LIGHT LIG IGHT GHT AUX UX LIGHT LIG T HEATT LIGHT press advances to minutes. Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F1 (cont.) Each TEMP press advances the time 15 minutes. FLTR1 SET JETS J TS S AUX AUX LIGHT LLIG IGHT T HEAT HEAT AT T Press LIGHT when finished. The read out scrolls the information that is now programmed. A 48 Press TEMP to exit to main screen. Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 Filter Cycle 2: Optional Filtration Filter Cycle 2 is OFF by default. It must be turned ON. The process is the same for setting F1. Once the BEGN (begin) screen displays, it is ready for more input. Revert back to “Adjusting Filtration Time Filter 1” above. Main Menu > FILT2 > OFF/ON > BEGN At the Main Screen, begin by pressing TEMP.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) Press TEMP to advance to the beginning of time setting the process for filtration. 2 JETS J TS S AUX UX LIGHT LIGHT HEAT HEAT ATT JETS J TS S If the display shows OFF, press TEMP again to witch the filtration mode to ON. FLTR 2 SET AUX AUX LIGHT LIG GHT HEAT HEAT AT Press TEMP to turn FILT2 ON FLTR 2 SET JETS J TS S 50 AUX AUX LIGHT LIGHT Press LIGHT to accept your choice to program F2.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) FLTR 2 JETS J TS AUX AUX LIGHT LIGH IGHT T JETS J TS AUX X LIGHT LIGH IGHT T 51 HEAT HEAT AT T FLTR 2 SET TEMP advances to the first screen to change time for F2. (BEGN will appear, which stands for begin.) The hour will flash. Press TEMP to change the hour. HEAT HEAT AT Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) Press LIGHT to advance to minutes. FLTR 2 P SET JETS J TS S AUX AUX LIGHT LIGH IGHT T JETS J TS S AUX AUX LIGHT LIGH LIG GHT T JETS J TS S AUX X LIGHT LIGH I T IGHT Press TEMP to change minutes. HEAT HEAT A AT FLTR 2 P SET 52 HEAT HEAT AT T FLTR 2 P SET SET Press LIGHT to set Run Hours. HEAT HEAT AT Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) FLTR 2 FLTR 2 JETS J S AUX X LIGHT LIG T HEAT HEATT JETS J S AUX X LIGHT LIG Press TEMP to begin hour change for F2. HEATT Each TEMP press increments the hours. FLTR 2 SET JETS J TS AUX UX LIGHT LIGHT FLTR 2 SET JETS J TS S 53 HEAT HEAT AT AUX UX LIGHT LI T LIGH LIGHT press advances to minutes. HEAT HEAT AT Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) JETS J TS S Each TEMP press advances the time 15 minutes. FLTR 2 SET AUX AUX LIGHT LIGH LIG IGHT T HEAT HEAT AT T Press LIGHT when finished. A The read out scrolls the information that had just been programmed. Press TEMP to exit to main screen. 54 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Adjusting Filtration Time for F2 (cont.) TEMP will flash hours to begin filtration programming for F2. FLTR1 JETS J S AUX AUX X LIGHT LIGH IGHT T HEAT HEAT AT T The hour will flash. Press TEMP to change the hour. SET FLTR1 JETS J S 55 AUX UX LIGHT LIGHT HEAT HEAT AT T P At this point, the time setting process is the same as for F1. Please revert back to “Adjusting Filtration Time for F1” above. Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Continuous Filtration (24 Hour Filtration) To set continuous filtration, set Filter 1 to begin at a specified time (it could be any time), and then to run for 24 hours. In this case, the filter 2 start time only controls when the second purge happens. Filter 2 end time will be unavailable. READY JETS J TS S AUX UX READY JETS J TS AUX AUX At the main screen, begin by pressing TEMP.
Transforming the Control of Hot Tubs Revolution Continuous Filtration (24 Hour Filtration, cont.) Press TEMP to advance to the beginning of the time setting process for filtration. 1 JETS J TS S AUX AUX LIGHT LLIG IGHTT HEAT HEAT ATT TEMP advances to the first screen to change time for F1. (BEGN will appear, which stands for begin.
Transforming the Control of Hot Tubs Revolution Continuous Filtration (24 Hour Filtration, cont.) FLTR1 JETS J S AUX UX LIGHT LIG GH FLTR1 HEAT HEATT JETS J S AUX X LIGHT LIG “RUN HRS” appears. Press TEMP to begin SET FLTR1 process. HEAT HEATT When the hours appear, advance those hours to 24 by pressing TEMP. FLTR1 SET JETS J TS S AUX AUX X LIGHT LIGH IGHT T HEAT HEAT ATT FLTR1 SET JETS J TS S 58 AUX A X LIGHT LIG GHT When 24 appears, press LIGHT.
Transforming the Control of Hot Tubs Revolution Continuous Filtration (24 Hour Filtration, cont.) JETS J TS S If needed, adjust the minutes to zero by pressing TEMP. FLTR1 SET AUX AUX LIGHT L LIGH T HEAT HEAT AT T Press LIGHT to exit. F 1 ENDS appears along with the start time, which is the same as the end time, of the filtration cycle (in this example 8:00 pm). Filtration cycle then begins again. SET 59 FLTR1 P To return to the main menu, press TEMP or wait approx. 30 seconds.
Transforming the Control of Hot Tubs Revolution General Messages 60 Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.
Transforming the Control of Hot Tubs Revolution Main Menu Reminder Messages TEMP Main Menu > PREF > Reminder MODE Reminder messages help in the general maintenance of the spa. TIME t Reminder Messages can be suppressed by using the PREF Menu. FLIP t Reminder Messages can be chosen individually by the Manufacturer. The OEM Spa Manufacturer may disable the messages entirely, or there may be a limited number of reminders on a specific model. t The frequency of each reminder (e.g.
Transforming the Control of Hot Tubs Revolution Suppressing Reminders This action allows you to suppress reminders. Main > PREF > Reminder READY JETS J S AUX AUX READY JETS J S AUX UX LIGHT LLIG GHT T HEAT AT T RANGE FLTR1 LIGHT LIG HEAT ATT The temperature flashes. JETS J TS S 62 AUX AUX Press TEMP to initiate a flashing display. RANGE FLTR1 LIGHT LLIG GHT T Press LIGHT repeatedly until PREF appears HEAT HEAT AT Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Suppressing Reminders (cont.) SET JETS J TS S AUX AUX LIGHT LIGH LIG IGHT T HEAT HEAT A AT JETS J TS S AUX X LIGHT LIG GH HEAT HEAT AT S “Reminders” scrolls across screen. JETS J TS S AUX X LIGHT LIG HEAT HEAT AT Press TEMP for options. 63 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Suppressing Reminders (cont.) TEMP toggles between No and Yes. SET JETS J TS S AUX UX LIGHT LIG IGHT GHT HEAT HEAT AT Press TEMP for options. 64 t Press LIGHT to exit the PREF menu. t Press LIGHT 3 times to return to MAIN menu. Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Reminder Messages (cont.) CHEK PH Check pH Alternates with temperature or normal display. Check pH with a test kit and adjust pH with the appropriate chemicals. Appears on a regular schedule, i.e. every 7 days. CHEK CHEM Check Chemistry Check sanitizer level and other water chemistry with a test kit and adjust with the appropriate chemicals. Appears on a regular schedule, i.e. every 7 days.
Transforming the Control of Hot Tubs Revolution Reminder Messages (cont.) TEST GFCI The GFCI is an important safety device and must be tested on a regular basis to verify its reliability. Appears on a regular schedule, i.e., every 30 days. Test GFCI Every user should know how to safely test the GFCI associated with the hot tub installation. A GFCI will have a TEST and RESET button on it that allows a user to verify proper GFCI function.
Transforming the Control of Hot Tubs Revolution Reminder Messages (cont.) TRT WOOD Treat Wood Alternates with temperature or normal display. Wood skirting and furniture should be cleaned and conditioned per the manufacturers instructions for maximum life. Appears on a regular schedule, i.e. every 180 days. Alternates with temperature or normal display. CHNG FLTR Change Filter Filters should be replaced occasionally to maintain proper spa function and sanitary conditions.
Transforming the Control of Hot Tubs Revolution Glossary Circ Pump (or circulation pump) Low horse power pump designated especially for maintenance of filtration and heating. It often runs all day. Clean-up (or purge) Cycle An action designed to circulate water to maintain sanitary conditions. Pumps or blowers purge standing water to prevent the water from becoming stagnant. Filtration Cycle Period of time designated to filter the system.
Transforming the Control of Hot Tubs Revolution Glossary (cont.) GFCI A device intended to protect people in the event of an electrical malfunction. Spa owners should know how to test the GFCI as routine maintenance. Preferences Programmed events according to personal preferences. SSID Software Self Identification Programming Setting an order and time for planned events, such as filter times, clean-up cycle, etc. 69 Manufactured under one or more of these patents. U.S.
Transforming the Control of Hot Tubs Revolution Glossary (cont.) Priming Mode Act of water flow through the plumbing to purge air from the spa system. Normally, priming mode can be bypassed. The priming mode is necessary only if the spa is refilled and if there’s the possibility of air being in the system. What Priming Mode does: Each time the spa is powered up, it will enter Priming Mode.
Index Symbols 2-Speed Pump 1 23 24 Hour Circulation Mode 23 24 hour clock 33 24 Hour Filtration 56 55911, Part No. 10 55914, Part No.
G M P general maintenance 61 General Messages 60 generator, ozone 40 GFCI 69 GFCI, Class A 5 Glossary 68 guard, VG Compliant suction 4 Main Menu 16 maintenance, general 61 Menu, Main 16 Messages, General 60 Messages, Reminder 61 Mode, 24 Hour Circulation 23 Mode, Circulation 23 Mode, Drain 28 Mode, Hold 27 Model, System 10 Mode, Priming 70 Mode, Ready 24, 38, 39, 42 Mode, READY 23 Mode -- Ready and Rest 23 Mode, Ready-in-Rest 24 Mode, Rest 24 Mode, REST 23 Modes, Circulation Pump 40 Panel Navigation 15
Range, Setting a High Temperature 19 Range, Setting a Low Temperature 20 Ready-in-Rest Mode 24 Ready Mode 24, 38, 39, 42 READY Mode 23 “ready to use” setting 18 Reminder Messages 61 Reminders, Suppressing 62 RESET, TEST and 66 Rest Mode 24 REST Mode 23 Restricting Panel Operation 29 Run Hours 52 S second filtration cycle 49 sensor, freeze 41 sensors, standard 41 sensors, temperature 41 sequence, Unlock 31 Series, TP Panel 14 SET READY 26 SET REST 26 set temperature 17, 23 Set Temperature 29 Setting a High T
Tustin Ca. 92780 (714) 384-0384 ©2010-2012 Balboa Water Group. All rights reserved. Manufactured under one or more of these patents. U.S. Patents: 5332944, 5361215, 5550753, 5559720, 5,883,459, 6253227, 6282370, 6590188, 6976052, 6965815, 7030343, 7,417, 74 834 b2, Canadian Patent: 2342614, Australian patent: 2373248 other patents both foreign and domestic applied for and pending. All material copyright of Balboa Water Group.