Operating instructions

FittheStandardFlueDivertersuppliedintotheholeinthetopoftheovenforunderventilationhood
installationandsecurewithscrews.Fordirectventing,FlueAdapterandDraftHoodmustbeplacedinto
theholeontopoftheoven.
Fourcasters(twowithwheelbrakes)andthemountinghardwarearepackedandincludedinthe
shipmentifordered.Installcasterswithwheelbrakesonthefrontoftheunit.Installationoftheunit
shouldbemadewithaconnectorthatcomplieswiththelatesteditionoftheStandardforConnectorsfor
MovableGasAppliancesANSIZ21.69intheUSA(CANCSA-6.16in Canada)andaquick-disconnect
devicethatcomplieswiththelatesteditionofthestandardforquickdisconnectdevicesforusewithgas
fuelANSIZ21.41intheUSA(CSA6.9inCanada).Adequatemeansmustbeprovidedtolimitthe
movementoftheappliancewithoutdependingontheconnectorandanyquickdisconnectdeviceorits
associatedpipingtolimitappliancemovement.
Therestraintshouldbeattachedtotherearlegsoftheovenonwhichcastersaremounted.If
disconnectoftherestraintisnecessary,therestraintshouldbeimmediatelyreconnectedafterthe
appliancehasbeenreturnedtoitsoriginallyinstalledposition.
Movetheoventoitsfinallocationkeepingtheminimumclearancefromthebackoftheoventothewall.
Thisclearanceisnecessaryforsafeoperationandtoprovideproperairflowtotheburnerchamber.
C.INSTALLATIONWITHCASTERS(OPTIONAL):RefertoFigure4
D.LOCATIONANDMINIMUMCLEARANCES:
MINIMUMCLEARANCESFROMCOMBUSTIBLEANDNONCOMBUSTIBLECONSTRUCTION
UnderVentilation Hood DirectVenting
RIGHTWALL 1” 1”
LEFTWALL 1” 3”
REARWALL 3” 3”
SUITABLEFORINSTALLATIONONCOMBUSTIBLEFLOORWHEN
INSTALLEDWITHLEGSORCASTERSPROVIDED.
! !
CAUTION:DONOTSETTHEOVENWITHITSBACKFLATAGAINSTTHE
WALL.ITWILLNOTOPERATEPROPERLYUNLESSTHEREISATLEAST
THREEINCHESBREATHINGSPACEBEHINDTHEOVEN
!
!
E.GASCONNECTION:
Theovensshouldnotbeinstalledonthesamegassupplylinewithspaceheaters,boilersorothergas
equipmentwithhighintermittentdemand.
Theinstallationoftheovenmustconformtothelatestlocalcodesor
Theappliancemustbeisolatedfromthegassupplypipingsystembyclosingitsmanualshut-offvalve
duringanypressuretestingofthegassupplypipingsystemattestpressuresequaltoorlesstha
psig(3.45kpa).Theapplianceanditsshut-offvalvemustbedisconnectedfromthegassupplypiping
systemduringanypressuretestingofthatsystemattestpressuresinexcessof½psig(3.45kpa).
Useapipejointcompoundthatisresistanttotheactionofliquefiedpetroleumgaseswhenmakinggas
connections.ForPropanegas,useatleast½(13mm)pipeortubingwitha5/8(16mm)inside
diameter.ForNaturalgas,use¾(19mm)pipe.
NationalFuelGasCode,ANSI
Z223.1,NaturalGasInstallationCode,CAN/CGA-B149.1,orthePropaneInstallationCode,
CAN/CGA-B149.2.